LC1D18P7 SQUARE D, LC1D18P7 Datasheet - Page 218

no-image

LC1D18P7

Manufacturer Part Number
LC1D18P7
Description
IEC Contactor
Manufacturer
SQUARE D
Datasheet

Specifications of LC1D18P7

No. Of Poles
3
Contact Configuration
3PST-NO
Relay Mounting
DIN Rail
Width
45mm
Relay Terminals
Screw Clamp
Operating Voltage
600VAC
Switching Power Ac1
3hp
Switching Power Ac3
15hp
Switching Current Ac1
32A
Switching Current Ac3
18A
Load Current Inductive
18A
Load Current Resistive
32A
LR9F Solid State Overload Relays - Characteristics
218
©
2001-2004 Schneider Electric All Rights Reserved
LR9F Solid State Overload Relays - Characteristics
Introduction
The LR9F solid state overload relay provides the accurate, repeatable protection of a solid state device,
while still maintaining the ease of installation of a traditional overload relay.
The LR9F provides protection against:
• Motor Overload
• Failure or Phase unbalance of 30% or greater
• Prolonged starting times
• Locked rotor conditions
The LR9F overload relays have 8 current ranges, spanning 30 amps up to 630 amps. They are available
in Class 10 trip or Class 20 trip models. The device is manually reset via a clearly labeled button on the
front face. A separate attachment is available for remote reset or test tripping of the relay. All units
incorporate both a normally open and normally closed contact for control circuit wiring.
The LR9F is designed to directly mount on the load side of a LC1F contactor, minimizing space and wiring
time. Lugs for the LR9F are ordered separately (see page 220 for selection). For LR9F relays up to 185 amps,
an interposing touch-safe terminal block may be ordered in place of lugs, making power wiring even easier.
1
7
LR9F Tripping Curve
Average operating times depending on multiples of the current setting
Class 10
1 Cold state curve
2 Hot state curve
1000
100
10
1
0
Tripping time in seconds
105
1
1,12 2
90
150
125
3
Ir(A)
ELECTRONIC MOTOR PROTECTION
4
1
2
5
6
X times current setting (Ir)
7
LR9 F5369
8
9
10
3
98
11
TEST
NO
12
TRIPPED
97
STOP
95
NC
RESET
Class 20
1000
100
10
96
1
0
Tripping time in seconds
1
1,12
6
5
4
2
2
1. Trip Current Adjustment Dial
2. Stop Button
3. Test Button
4. Reset Button
5. Trip Indicator
6. Clip-on Legend
7. Transparent Cover with Sealing Provisions
3
4
X times current setting (Ir)
5
1
2
6
7
8
9
08/04