C500CN122N Omron, C500CN122N Datasheet - Page 30

no-image

C500CN122N

Manufacturer Part Number
C500CN122N
Description
I/O CONNECTION CABLE
Manufacturer
Omron
Datasheet

Specifications of C500CN122N

Leaded Process Compatible
No
Peak Reflow Compatible (260 C)
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
I/O Power Supply
3G2A5-PS222-E
3G2A5-PS212-E
Mounting screw
Do not loosen this screw.
Fuse holder
Contains a MF61NR fuse
(3 A, 250 V, 6.35-dia. x32)
POWER indicator
Lights when power is supplied.
Mounting screw
Do not loosen this screw.
Mounting screw
Do not loosen this screw.
Fuse holder
Contains a MF61NR fuse
(4 A, 125 V, 6.35-dia. x32)
POWER indicator
Lights when power is supplied.
Mounting screw
Do not loosen this screw.
Terminals for
external connections
Terminals for
external connections
0.8 A, 24 VDC output
+
-
Voltage selector
Short: 100 to 120 V
Open: 200 to 240 V
+
-
AC input
LG
GR
LG
GR
24 VDC input
Connect a 100 to 120 VAC or 200 to
240 VAC power source
Short these terminals to select 100 to
120 VAC. Open them to select 200 to
240 VAC.
Ground this terminal at a resistance
of less than 100 W to improve noise
immunity or prevent electric shock.
Ground this terminal at a resistance
of less than 100 W to prevent electric
shock.
Use these terminals to supply power
to DC Input Units. Use a separate
Power Supply if the I/O Unit operate
on more than 0.8 A. If a current higher
than 0.8 A is output, the PC stops.
These terminals are used to supply
external DC Input Units. If the Unit
requires more than 0.8 A a separate
supply must be used. The PC shuts off
automatically if a current of more than
0.8 A is drawn from the supply.
Connect a 24-VDC power source
(2.3 A min.)
Ground this terminal at a resistance
of less than 100 W to improve noise
immunity or prevent electric shock.
Ground this terminal at a resistance
of less than 100 W to prevent electric
shock.
Section 2-5
17

Related parts for C500CN122N