CV500BC101 Omron, CV500BC101 Datasheet - Page 149

no-image

CV500BC101

Manufacturer Part Number
CV500BC101
Description
Programmable Logic Controller
Manufacturer
Omron
Datasheet

Specifications of CV500BC101

Peak Reflow Compatible (260 C)
No
Leaded Process Compatible
No
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Precautions
124
Setting Data Links
C200HX/HG/HE, CS/CJ-series, CVM1, CV-series, and CQM1H-series PLCs
have different-sized memory areas. When data links are manually set, pro-
vided the PLCs are set so as not to receive data in the areas indicated in the
following diagram, the data link setting area is not limited by the small area
size of the PLC.
If the LR Area in the C200HX/HG/HE or CQM1H Series is manually set for a
data link with a CVM1, CV-series or CS/CJ-series PLC, the LR words will be
linked to CIO 1000 to CIO 1063 in the CVM1, CV-series or CS/CJ-series PLC.
CIO 1064 to CIO 1199 cannot be linked with C200HX/HG/HE or CQM1H-
series PLCs in this way.
Example:
c) Refer to the Controller Link Support Boards Operation Manual
d) If CX-Net detects an error during the data link table check, trou-
LR00
LR63
C200HX/HG/HE and
CQM1H-series PLCs
(Data link start word – 1) + Total number of send/receive
words in area
(W307) for information on the Controller Link Support Board.
bleshoot the error referring to 9-4 Troubleshooting Error Mes-
sages in CX-Net Data Link Table Check .
to
C200HX/HG/HE and
CQM1H-series PLCs
235
to
0
247 (IR Area)
63 (LR Area)
5999 (DM Area)
6143 (EM Area)
1000
1063
1064
1199
CVM1, CV-series or
CS/CJ-series PLCs
to
to
100
335
336
CVM1 and
CV-series PLCs
Cannot be directly linked
with C200HX/HG/HE or
CQM1H words.
CS/CJ-series PLCs
200
435
436
Section 5-2

Related parts for CV500BC101