ELC-GP04-03 EATON CUTLER HAMMER, ELC-GP04-03 Datasheet - Page 57

Graphics Panel

ELC-GP04-03

Manufacturer Part Number
ELC-GP04-03
Description
Graphics Panel
Manufacturer
EATON CUTLER HAMMER
Datasheet

Specifications of ELC-GP04-03

No. Of Functions
10
Pixel Format
128 X 64
For Use With
ELC Logic Controllers
February 2007
Product Description
The Cutler-Hammer
nologies (IT). Ethernet Modbus
Adapter (D77D-EMA) from Eaton’s
electrical business has greatly
increased the functionality of Cutler-
Hammer IT. communicating products,
allowing monitoring and control for IT.
I/O and IT. motor control devices. The
adapter concentrates all data from
these devices into a single Modbus
node.
The Modbus Adapter supports not
only Modbus TCP but also Modbus
serial (ASCII and RTU) as a slave
device. This combination of the two
physical layers provides for ultimate
functionality when connecting to a
Modbus system. A unique attribute of
the D77D-EMA is that it supports Mod-
bus serial Pass-Through. In this mode
a customer can connect Modbus serial
devices to one of the QCPort channels
and monitor and control them over
Modbus TCP.
To simplify the configuration of the
D77D-EMA, a simple auto-configure
button press sets the system up for
default operation. This automatically
configures the Modbus registers to the
QCPort system devices.
Application Description
In a typical Modbus Adapter applica-
tion, the D77D-EMA connects directly
to Modbus, and resides in a system
with IT. I/O and other communicating
motor controls. The data from these
IT. devices is assembled into input and
output registers before being pre-
sented to Modbus.
CA05001001K
Cat. No. D77D-EMA
®
Intelligent Tech-
For more information visit: www.EatonElectrical.ca
Features, Functions and Benefits
Standards and Certifications
Approvals
Table 85. Approvals/Certifications
Electrical/EMC
Other Approvals
Technical Data and Specifications
Table 86. Environmental Ratings
Transportation/Storage
Operating
Description
ESD Immunity (IEC 61000-4-2)
Radiated Immunity (IEC 61000-4-3)
Fast Transient (IEC 61000-4-4)
Surge (IEC 61000-4-5)
RF Conducted (IEC 61000-4-6)
Magnetic Field (IEC 61000-4-8)
Ingress Protection Code
Radiated and Conducted Emissions EN 5011 Class A
Agency Certifications
Description
Temperature
Humidity
Temperature
Humidity
Altitude
Shock
(IEC 68-2-27)
Vibration
(IEC 68-2-6)
Pollution Degree
Communication to Modbus
consuming one address
Supports Boot P and static IP
addressing
10 BaseT Connection
RS-485 Modbus slave serial
connection
Supports Serial Modbus Pass-
Through over Modbus TCP
Provides for control of all IT. com-
municating devices connected to
the gateway
Manually set to address and baud
rate for serial Modbus; configura-
tion using a software application is
not required for normal operation
Single button press auto configures
the gateway, setting up the system
for default operation
PLC, I/O & Communications Products
IT. Connect
Communication Adapters (D77D Series) — Modbus Adapter
consult factory
15G any direction for
11 mS
5 – 150 Hz, 5G .7 mm
maximum peak-to-peak
Specification
-58° – 176°F (-50° – 80°C)
5 – 95% non-condensing
-13° –149 °F (-25° – 65°C)
5 – 95% non-condensing
Above 6,600 ft. (2,000m)
2
Specification
± 8 kV air, ± 4 kV contact
10V/m 80 – 1,000 MHz, 80% amplitude modulation @ 1 kHz
± 2 kV supply and control, ± 1 kV communications
± 1 kV line-to-ground, ± 2 kV line-to-line
10V, .15 – 80 MHz
30A/m, 50 Hz
IP20
UL 508, CUL (CSA C22.2 No. 14), CE (Low Voltage Directive),
Modbus Conformance Tested
Table 87. Modbus Specifications
Description
Connections
I/O Size
Baud
Addressing
QCPort Channels 2 Independent
Advanced configuration using
CH Studio
Provides for backplane and inter-
connect cable connections to
QCPort
Two independent QCPort (commu-
nication) ports
Powered from QCPort
Isolated from Modbus
Status LEDs for Modbus, QCPort
and module health
Provides for configuration of QCPort
devices over Modbus TCP
Small package size
DIN rail mountable
RS-485
1024 Registers Output
Ethernet 10 Megabit
Serial 1200 to 115.2K baud
Serial – DIP Switch 1 – 255
Channels
Specification
10 BaseT
1024 Registers Input
Ethernet – Boot P or Static IP
57