IAMA3535 Red Lion Controls, IAMA3535 Datasheet

Isolation Amplifier

IAMA3535

Manufacturer Part Number
IAMA3535
Description
Isolation Amplifier
Manufacturer
Red Lion Controls
Datasheets

Specifications of IAMA3535

Supply Voltage Ac, Min
0V
Supply Voltage Dc, Min
11V
Width
3.12"
Signal Input Type
Selectable Current Or Voltage
Configuration Setup
DIP Switch
Iso-amp Mounting Type
DIN Rail
Supply Voltage Dc, Max
36V
Input Accuracy
± 0.1% Of FS
Signal Output Type
Selectable Current Or Voltage
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
MODEL IAMA - UNIVERSAL SIGNAL CONDITIONING MODULE
GENERAL DESCRIPTION
convert over 100 combinations of analog signal ranges. The IAMA3535
converts and transmits signals linearly proportional to the input, while the
IAMA6262 transmits the scaled square root of the input signal. This allows the
IAMA6262 to provide a signal that is linear to flow rate in applications utilizing
a differential pressure transducer.
modules for each input and output signal range, and allows quick and
convenient setup for over 100 standard signal conversions. By utilizing the
Field mode of calibration, the user can customize the input and output scaling
for odd applications, including reversal of the output relative to the input.
optically isolated Input/Output signal circuits and transformer isolated Power to
Input, Power to Output circuits.
upon range selection and scaling. The microprocessor based design provides
ease of field scaling and the onboard E
recall. Both models come factory precalibrated for all input and output ranges.
Factory or custom field scaling can be selected by a simple mode switch change.
The IAMA can be factory recalibrated in the field if desired.
DIN rail mounting saves time and panel space. The units are equipped with
universal mounting feet for attachment to standard DIN style rails, including top
hat profile rail according to EN50022 - 35x7.5 and 35 x 15 and G profile rail
according to EN50035-G32.
DIMENSIONS In inches (mm)
The IAMA – Universal Signal Conditioning Module Series can isolate and
DIP switch range selection eliminates the need to order and stock different
In addition to the conversion capabilities, the IAMA modules feature
The modules’ overall full scale accuracy typically exceed 0.05% depending
The modules’ environmental operating temperature range is -20°C to +65°C.
MC2279X
(79.2)
3.12
2
PROM stores scaling values for future
(27.5)
1.08
IAMA
MC2290C
A
S
T
T
U
S
1
 3-WAY ISOLATION OF ANALOG SIGNALS
 UNIVERSAL CONVERSION MODULE - INPUTS AND OUTPUTS
 OVER 100 INPUT AND OUTPUT ANALOG CONVERSION
 CHOOSE LINEAR OR SQUARE ROOT EXTRACTION MODEL
 ALL RANGES ARE FACTORY PRECALIBRATED. CUSTOM FIELD
 11 to 36 VDC AND 24 VAC MODULE POWER
SAFETY SUMMARY
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
ORDERING INFORMATION
SPECIFICATIONS
1. POWER: 11 to 36 VDC, 3 W max. or 24 VAC, 10%, 50/60 Hz, 4.8 VA max.
2. INPUT/OUTPUT RANGES: See Tables 2 and 3
3. ZERO/SPAN ADJUSTMENTS: Digital (DIP Switch Transition)
4. MAX INPUT SIGNAL:
5. INPUT RESISTANCE:
6. INPUT PROTECTION: Surge suppressor diodes
7. MAX OUTPUT CURRENT:
8. LOAD RESISTANCE:
9. OUTPUT COMPLIANCE:
10. ISOLATION LEVEL INPUT TO OUTPUT: 1.5 kV @ 50/60 Hz, 1 min
11. STEP RESPONSE: To within 99% of full scale: 300 msec
12. ACCURACY (INCLUDING LINEARITY): Factory: ±0.1% of span
13. RESOLUTION: 0.01% full scale input, 0.01% full scale output
MODEL NO.
SELECTED VIA DIP SWITCH SETTINGS
COMBINATIONS
CALIBRATION IS AVAILABLE FOR ALL RANGES WHILE
MAINTAINING THE FACTORY CALIBRATION FOR FUTURE USE
All safety related regulations, local codes and instructions that appear in the
to installation and operation of the unit.
Current Input: 110 mA DC, 1.1 VDC
Voltage Inputs: Terminal 7- 1 VDC +10%
Current: 10 
Voltage: > 100 K
Current Output: 22 mA
Voltage Output: 10 mA
Current Output:  600 
Voltage Output:  1 K
Current: 4 to 20 mA, 0 to 20 mA: 12 V min ( 600 )
Voltage: 10 VDC across a min. 1 K load (10 mA). Factory calibrated for
max. for all ranges except 1 mA, 2 mA, and 20 mV. These ranges are
accurate to ±0.2% of span max. All ranges can be field calibrated to 0.1%
of span max.
IAMA
loads of > 1 M.
Read complete instructions prior
CAUTION: Risk of Danger.
0 to 1 mA: 10 V min (10 K)
Square Root Universal Signal Conditioning Module
Linear Universal Signal Conditioning Module
UL Recognized Component,
File # E179259
Terminal 8- 10 VDC +10%
Terminal 9- 100 VDC +10%
DESCRIPTION
CAUTION: Risk of electric shock.
Bulletin No. IAMA-G
Drawing No. LP0413
Released 04/09
PART NUMBER
IAMA3535
IAMA6262

Related parts for IAMA3535

IAMA3535 Summary of contents

Page 1

... GENERAL DESCRIPTION The IAMA – Universal Signal Conditioning Module Series can isolate and convert over 100 combinations of analog signal ranges. The IAMA3535 converts and transmits signals linearly proportional to the input, while the IAMA6262 transmits the scaled square root of the input signal. This allows the IAMA6262 to provide a signal that is linear to flow rate in applications utilizing a differential pressure transducer ...

Page 2

... DC/DC transformer isolation circuit. OVERVIEW The IAMA3535 continuously monitors a voltage or current input and provides a linearly proportional voltage or current output, while the IAMA6262 transmits the scaled square root of the input signal. This allows the IAMA6262 to provide a signal that is linear to flow rate in applications utilizing a differential pressure transducer ...

Page 3

CHECKSUM ERRORS A checksum is performed every time power is applied to the IAMA checksum error occurs, the LEDs will indicate where the error occurred according to Table 1, LED Indications. Operation with a checksum error is not ...

Page 4

POWER AND OUTPUT CONNECTIONS Power Primary power is connected to terminals 2 and 3 (labeled VDC- and VDC+). For best results, the Power should be relatively “clean” and within the specified variation limits. Drawing power from heavily loaded circuits or ...

Page 5

INPUT SCALING USING FIELD CONFIGURATION ~ - DC- (AC DC+ OUT (AC) V OUT OUT OUT+ MC2290D IAMA U S 10V ...

Page 6

OUTPUT SCALING USING FIELD CONFIGURATION ~ - DC- (AC DC+ I OUT (AC) V OUT OUT OUT MC2290D IAMA U S 10V 1V ...

Page 7

RECALIBRATING FACTORY STORED VALUES WARNING: Read the complete procedure at least once before attempting to recalibrate the factory values. This procedure should only be performed due to factory checksum error or unacceptable error. This procedure should be performed by qualified ...

Page 8

... The Company disclaims all liability for any affirmation, promise or representation with respect to the products. The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries, deaths, property ...