MCR-FL-C-UI-UI-DCI-24/230 Phoenix Contact, MCR-FL-C-UI-UI-DCI-24/230 Datasheet

no-image

MCR-FL-C-UI-UI-DCI-24/230

Manufacturer Part Number
MCR-FL-C-UI-UI-DCI-24/230
Description
INTERFACE ANALOG
Manufacturer
Phoenix Contact

Specifications of MCR-FL-C-UI-UI-DCI-24/230

Input Type
Configurable
Output Type
Configurable
No. Of Output Channels
1
Accuracy
± 0.1%
Supply Voltage Range
20V To 253V
Power Consumption
2VA
Approval Bodies
UL Recognised
External Depth
114.5mm
External
RoHS Compliant
External Length / Height
99mm
Rohs Compliant
Yes
Configurable 3-Way Isolation Amplifier
With Long-Range Supply
MCR-FL-C-UI-UI-DCI-24/230
• 3-way isolation
• Safe isolation in accordance with EN 61 010
• Configurable inputs and outputs
• Adjustable cut-off frequency <10 Hz / 10 kHz,
• Operating voltage 20...253 V AC/DC
• 12.5 mm (0.492 in.) ME Housing
1. Description
3-way standard signal isolation amplifier can process
0…20 mA, 4…20 mA and 0…10 V standard signals
on the input side.
supply is set up as "safe isolation" with a test voltage of
4 kV . Depending on the application, the signal
transmission cut-off frequency can be set as either 10
kHz (approximately) or as a< 10 Hz filter. On the output
side, any of the three standard signals are available.
Adjustment after configuration is not necessary, as
each transmission variant is calibrated and stored in
the device. The transmission error is always
< 0.1%.
long-range supply of 20…253 V AC/DC and is available
in 12.5 mm (0.492 in.) narrow housing with pluggable
screw connection.
Headquarters: © Phoenix Contact GmbH & Co. KG • Flachsmarktstraße 8 • 32825 Blomberg • Germany
approximately
The configurable MCR-FL-C-UI-UI-DCI-24/230
The 3-way isolation between signal input, output and
The 3-way standard signal isolation amplifier has a
Phone +49 - 52 35 - 3 00 • Fax +49 - 52 35 - 34 12 • www.phoenixcontact.com
U,
I
POWER
U,
I

Related parts for MCR-FL-C-UI-UI-DCI-24/230

MCR-FL-C-UI-UI-DCI-24/230 Summary of contents

Page 1

... ME Housing POWER 1. Description The configurable MCR-FL-C-UI-UI-DCI-24/230 3-way standard signal isolation amplifier can process 0…20 mA, 4…20 mA and 0…10 V standard signals on the input side. The 3-way isolation between signal input, output and supply is set up as "safe isolation" with a test voltage ...

Page 2

... Configurable 3-Way Isolation Amplifier With Long-Range Power Supply – MCR-FL-C-UI-UI-DCI-24/230 2. Technical Data IN OUT GND GND fixed flexible 2 [mm ] AWG Connection data 0.2-2.5 0.2-2.5 24-14 Description MCR 3-Way isolation amplifier , for electrical isolation of analog signals Technical Data Input Input signal ...

Page 3

... Configurable 3-Way Isolation Amplifier With Long-Range Power Supply – MCR-FL-C-UI-UI-DCI-24/230 Conforms to the EMC Directive 89/336/EEC and the Low Voltage Directive 73/23/EEC EMC (electromagnetic compatibility) Noise immunity in accordance with EN 50082-1/EN 50082-2 • Electrostatic discharge (ESD) • Electromagnetic HF field Amplitude modulation Pulsed modulation • ...

Page 4

... Configurable 3-Way Isolation Amplifier With Long-Range Power Supply – MCR-FL-C-UI-UI-DCI-24/230 3. Configuration 3.1. Opening the Device (Figure 06) The locked housing cover is released on both sides using a screwdriver 1 . The housing cover and electronics can now be pulled out 2 . Ensure you take sufficient measures against electrostatic discharge 3 ...

Related keywords