CS1W-CN713 Omron, CS1W-CN713 Datasheet - Page 147

no-image

CS1W-CN713

Manufacturer Part Number
CS1W-CN713
Description
"CABLE CS1 EXP I/O,70cm"
Manufacturer
Omron
Datasheet

Specifications of CS1W-CN713

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
I/O Unit Wiring Precautions
Leakage Current
(24 V DC)
!Caution Always use crimp connectors for wiring. Do not connect bare stranded wires
!Caution To satisfy the EC directives (low-voltage directive), provide reinforced insula-
!Caution Install external breakers and take other safety measures against short-circuit-
!Caution Double-check all the wiring before turning ON the power supply. Incorrect wir-
!Caution Do not apply voltages exceeding the input voltages to Input Units or voltages
directly to terminals.
tion or double insulation on the I/O Units’ DC power supply.
ing in external wiring. Insufficient safety measures against short-circuiting
may result in burning.
ing may result in burning.
exceeding the switching capacity to Output Units. Doing so may result in dam-
age or destruction of the I/O Unit or result in fire.
When two-wire sensors, such as photoelectric sensors, proximity sensors, or
limit switches with LEDs, are used, the input bit may be turned ON errone-
ously by leakage current. If the leakage current exceeds 1.3 mA, insert a
bleeder resistor in the circuit to reduce the input impedance, as shown in the
following diagram.
2-wire method
sensor, etc.
R = 7.2/(2.4 I–3) k max.
W = 2.3/R W min.
The equations above were derived from the following equation:
W
I
Input voltage (24)/R
R
R +
Input voltage (24)
Input current (10)
Input voltage (24)
Input current (10)
Input voltage (24)
I: Device's leakage current (mA)
R: Bleeder resistance (k )
W: Bleeder resistor's power rating (W)
Bleeder resistor
Input power
supply
OFF voltage (3)
margin (4)
R
CQM1H
Section 4-8
125