88 970 117 Crouzet USA, 88 970 117 Datasheet - Page 3

M3 MODEM INTERFACE

88 970 117

Manufacturer Part Number
88 970 117
Description
M3 MODEM INTERFACE
Manufacturer
Crouzet USA
Datasheet

Specifications of 88 970 117

Ip/nema Rating
IP20, IP40
Svhc
No SVHC (18-Jun-2010)
Approval Bodies
CSA, UL
External Depth
70mm
External Length / Height
90mm
Mounting Type
DIN Rail
Supply Voltage
RoHS Compliant
Supply Voltage Max
24VDC
Rohs Compliant
Yes
For Use With
Remote Control Application
14/01/2010
Characteristics of relay outputs common to the entire range
Characteristics of product with DC power supplied
Supply
Digital inputs (I1 to IA and IH to IY)
Analogue or digital inputs (IB to IG)
Inputs used as analogue inputs
Response time with function blocks programming
Maximum counting frequency
Sensor type
Input type
Isolation between power supply and inputs
Isolation between inputs
Protection against polarity inversions
Status indicator
Max. breaking voltage
Breaking current
Electrical durability for 500 000 operating cycles
Max. Output Common Current
Minimum switching capacity
Minimum load
Maximum rate
Mechanical life
Voltage for withstanding shocks
Response time
Built-in protections
Status indicator
Nominal voltage
Operating limits
Immunity from micro power cuts
Max. absorbed power
Protection against polarity inversions
Input voltage
Input current
Input impedance
Logic 1 voltage threshold
Making current at logic state 1
Logic 0 voltage threshold
Release current at logic state 0
Response time
Maximum counting frequency
Sensor type
Conforming to IEC/EN 61131-2
Input type
Isolation between power supply and inputs
Isolation between inputs
Protection against polarity inversions
Status indicator
CB12-CD12-XD10-XB10
CB20-CD20-XB26-XD26
Measurement range
Input impedance
Input voltage
Value of LSB
Input type
Resolution
Conversion time
Accuracy at 25°C
Configurable in increments of 10 ms
50 ms min. up to 255 ms
State 0 →1 (50/60 Hz)
In accordance with cycle time (Tc) and input response time (Tr) :
1/ ( (2 x Tc) + Tr)
Contact or 3-wire PNP
Resistive
None
None
Yes
On LCD screen for CD and XD
5 →30 V DC
24 →250 V AC
CB-CD-XB10-XD10-XR06-XR10: 8 A
XD26-XB26: 8 x 8 A relays, 2 x 5 A relays
XE10: 4 x 5 A relays
XR14: 4 x 8 A relays, 2 x 5 A relays
Usage category DC-12: 24 V, 1.5 A
Usage category DC-13: 24 V (L/R = 10 ms), 0.6 A
Usage category AC-12: 230 V, 1.5 A
Usage category AC-15: 230 V, 0.9 A
12A for O8,O9,OA
10 mA (at minimum voltage of 12 V)
12 V, 10 mA
Off load: 10 Hz
At operating current: 0.1 Hz
10,000,000 operations (cycles)
In accordance with IEC/EN 60947-1 and IEC/EN 60664-1: 4 kV
Make 10 ms
Release 5 ms
Against short-circuits: None
Against overvoltages and overloads: None
On LCD screen for CD and XD
12 V DC
-13% / +20%
or 10.4 V DC < 14.4 V DC (including ripple)
≤ 1 ms (repetition 20 times)
CB12 with solid state outputs: 1.5 W
CD12: 1.5 W
CD20: 2.5 W
XD26-XB26: 3 W
XD26-XB26 with extension: 5 W
XD26 with solid state outputs: 2.5 W
Yes
12 V DC (-13% / +20%)
3,9 mA @ 10,44 V DC
4,4 mA @ 12,0 V DC
5,3 mA @ 14,4 VDC
2.7 kΩ
≥ 7 V DC
≥2 mA
≤ 3 V DC
<0.9 mA
1 →2 cycle times
I1 & I2: Ladder (1 kHz) & FBD (Up to 6 kHz)
I3 to IA & IH to IY: in accordance with cycle time (Tc) and input response time (Tr) : 1/ ( (2 x Tc) + Tr)
Contact or 3-wire PNP
Type 1
Resistive
None
None
Yes
On LCD screen for CD and XD
4 inputs IB →IE
6 inputs IB →IG
(0 →10 V) or (0 →V power supply)
14 kΩ
14.4 V DC max
14 mV, 4 mA
Common mode
10 bit at maximum input voltage
Controller cycle time
± 5%
www.crouzet.com