UPL1-1-72-103 AIRPAX, UPL1-1-72-103 Datasheet - Page 14

CIRCUIT PROTECTOR, HYD-MAG, 1P, 250V 10A

UPL1-1-72-103

Manufacturer Part Number
UPL1-1-72-103
Description
CIRCUIT PROTECTOR, HYD-MAG, 1P, 250V 10A
Manufacturer
AIRPAX
Series
UPLr
Datasheet

Specifications of UPL1-1-72-103

Input Voltage Vac
250V
No. Of Poles
1
Current Rating
10A
Interrupting Capacity
5kA
Dielectric Strength
1.5kV
Trip Time
20s
Voltage Rating Vdc
65V
Leaded Process Compatible
Yes
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
180
Trip free
Will trip open on overload, even when the handle is forcibly
held on or restrained. This prevents operator from damaging
the circuit by holding the handle in the ON position.
Trip Indication
The operating handle moves positively to the OFF position on
overload.
Ambient Operation
Operates normally in temperatures between –40°C and +85°C.
Insulation Resistance
Not less than 100 megohms at 500Vdc.
Dielectric Strength
Withstands 1500Vac at 60Hz for 60 seconds or 1800Vac for
one second from terminal to terminal, and from auxiliary
switch terminal to main terminal.
endurance
Per UL 1077 (6000 operations at rated load plus 4000
operations with no load). Tested at a maximum rate of 6 times
per minute. rating above 50 amperes operate a minimum of
5000 operations.
Shock
Withstands 100G or more without tripping while carrying full
rated current per MIL-Std-202, Method 213, Test Condition I.
Instantaneous types (delay 40, 50, 60 and 49, 59, 69) and dual
coil configurations are tested at 80% of rated current.
Protectors mounted in the handle down position are to be
tested with no current applied (per MIL-PrF-55629).
Vibration
Withstands 10G without tripping while carrying full rated
current per MIL-Std-202, Method 204, Test Condition A.
Instantaneous types (delay 40, 50, 60 and 49, 59, 69) and dual
coil configurations are tested at 80% of rated current.
APL/UPL SPECIFICATIONS
APPROxIMATe WeIgHT PeR POLe
APL/UPL, 205/295 - APL/UPL Specifications
Ounces
3.7
grams
103
Dual Coil Ratings
5-65Vdc and 5-250Vac for three terminal configurations.
5-120Vac and 5-120Vdc for four terminal configurations. Not
available in delays 64, 65 and 66.
APL Ratings
0.050-50 amperes, 65Vdc, 250Vac maximum, 50/60Hz or 400Hz.
51-100 amperes at 65Vdc and 120Vac maximum. ratings of
0.050-20 amperes at 277Vac, 50/60Hz are available upon
request.
Auxiliary Switch Ratings (APL/UPL, 205/295)
rEC4 and rEC5 are rated at 10 amperes, 250Vac or 3
amperes, 50Vdc. rEG4 and rEG5 are rated at 0.1 amperes,
125Vac.
UPL Ratings
UPL protectors are UL STD. 1077 (File No. E-66410) and CSA
STD. C22.2–No. 235 (File No. Lr-26229) recognized as
supplementary protectors in the following configurations and
ratings. Consult factory for further information.
Configurations
Series, Shunt, relay, Auxiliary Switch, Switch Only, Dual Coil,
No Voltage.
Poles
One through nine.
Moisture Resistance
Designed to meet the requirements of MIL-PrF-55629 when
tested in accordance with Method 106 of MIL-Std-202.
Salt Spray (Corrosion)
Designed to meet the requirements of MIL-PrF-55629 when
tested in accordance with Method 101 of MIL-Std-202.
Where applicable, mechanical support must be provide to the terminals when
applying torque
ReCOMMeNDeD TORQUe SPeCIfICATIONS
10-32 Screw Terminals
1/4 - 20 Stud Terminals
6-32 Mounting Inserts
M3 Mounting Screws
M5 Stud Terminals
Component
http://airpax.sensata.com/
Torque (in-lbs)
13 to 14
13 to 14
25 to 30
6 to 8
4 to 5

Related parts for UPL1-1-72-103