460-480 Tyco Electronics, 460-480 Datasheet - Page 113

Voltage Transformer

460-480

Manufacturer Part Number
460-480
Description
Voltage Transformer
Manufacturer
Tyco Electronics
Series
460r
Datasheet

Specifications of 460-480

Turns Ratio
4
Transformer Mounting
Chassis
Voltage Ratio
480
Primary Voltages
480V
Power Rating
150VA
Output Voltage
120V
Mounting Type
Foot Mounted
Transformer Type
Voltage
Lead Free Status / RoHS Status
na
Model 468
• Terminals are brass studs No. 10–32 with one lockwasher, flatwasher and regular nut.
• These transformers are designed for operation line-to-line. They may also be operated
• It is desirable to use a 0.80 amp fuse in the secondary to protect the transformer.
• With two exceptions these transformers are ANSI C57.13 group 1.
• Models 468–380, 468-400, 468–416 designed specifically for 50Hz operation are available
• Each transformer has two plastic terminal covers.
• The core and coil assembly is encased in a thermoplastic shell and filled with resin.
• Approximate weight: 4 lbs
line-to-ground or line-to-neutral at reduced voltage, (58% of rated volts).
Those marked * are group 2.
with reduced performance – consult factory for details.
Catalogue Number
*468–480
*468–600
467–069
468–069
468–120
468–208
468–240
468–277
468–288
468–300
468–346
Voltage Rating
*480:120
*600:120
69.3:120
69.3:120
300:120
208:120
240:120
346:120
288:120
277:120
120:120
0.58:1
0.58:1
Turns Ratio
2.88:1
2.31:1
1.73:1
2.4:1
2.5:1
4:1
2:1
5:1
1:1
Rec. Primary Fuse Rating
0.75
0.75
0.75
0.50
0.40
3.0
2.0
1.5
1.0
1.0
1.0
Frequency:
50Hz
Standard Secondary Voltage:
120 Volts
Insulation Level:
600 Volts, 10kV BIL full wave
Accuracy Class:
±0.6 at all burdens up to 7.6VA
at 1.5% with 20VA burden.
Thermal Rating:
75VA at 30°C amb
50VA at 55°C amb
CSA 223647
Approvals
UL 257877
113