Specifications of 460-480

Turns Ratio
4
Transformer Mounting
Chassis
Voltage Ratio
480
Primary Voltages
480V
Power Rating
150VA
Output Voltage
120V
Mounting Type
Foot Mounted
Transformer Type
Voltage
Lead Free Status / RoHS Status
na
Secondary Turn Ratio Modification
Application Guide
Formula:
Where:
Example: A 300:5 Current Transformer –
(In practicality one turn is dropped from the secondary as a ratio correction factor.)
The ratio of the current transformer can be modified by altering the number of secondary
turns by forward or backwinding the secondary lead through the window of the current
transformer.
By adding secondary turns the same primary amperage will result in a decrease in
secondary output. By subtracting secondary turns the same primary amperage will result in
greater secondary output.
Again using the 300:5 example adding five secondary turns will require 325 amps on the
primary to maintain the 5 amp secondary output or
Deducting 5 secondary turns will only require 275 amps on the primary to maintain the 5
amp secondary output or
The above ratio modifications are achieved in the following manner:
To add secondary turns, the white lead should be wound through the CT from the side
opposite the polarity mark.
To subtract secondary turns the white lead should be wound through the CT from the same
side as the polarity mark.
1p
–––
1s
lp
ls
Np
Ns
300p
–––––
5s
325p
–––––
5s
275p
–––––
5s
=
=
=
=
Ns
–––
Np
Primary Amperage
Secondary Amperage
Number of Primary Turns
Number of Secondary Turns
60s
–––
1p
65s
–––
1p
55s
–––
1p