Specifications of G9SB-3012-A

Contact Form
3PST - NO
Coil Voltage
24 VAC/VDC
Contact Rating
5 A
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Ultra Slim Safety Relay Unit
Model Number Structure
Model Number Legend
1. Function
2. Contact Configuration (Safety Output)
3. Contact Configuration (OFF-delay Output)
4. Contact Configuration (Auxiliary Output)
Ordering Information
Note: 1. Relays with inverse inputs are used mainly when inputting signals from two mechanical switches.
* The G9SB-3010 can be applied to Safety Category 3 of the EN954-1 if double breaking is used.
G9SB-@@@@@-@
• Models of width 17.5 mm available with 2 or 3 poles. Models of
• Conforms to EN standards. (TÜV approval)
• DIN track mounting possible.
Main contacts
Safety Relay Unit
G9SB
width 22.5 mm with 3 poles also available.
None: Emergency stop
2:
3:
0:
0:
1:
DPST-NO
3PST-NO
2. Relays with positive commons are used mainly when inputting signals from a safety sensor or from one mechanical switch.
Be sure to read the “Safety Precautions” on page 8.
DPST-NO
3PST-NO
None
None
SPST-NC
1 2 3 4 5
SPST-NC
Auxiliary
contact
None
6
Number of input channels
1 channel or 2 channels
1 channel or 2 channels
1 channel or 2 channels
1 channel or 2 channels
(direct breaking)
2 channels
2 channels
2 channels
2 channels
None
Note: Please see “Ordering Information” below for the actual models that can be ordered.
Reset mode
Auto-reset
Manual reset
Auto-reset
Manual reset
5. Input Configuration
6. Miscellaneous
None: 1-channel or 2-channel input possible
0:
2:
A:
B:
C:
D:
None (direct breaking)
2-channel input
Auto-reset, inverse input
Auto-reset, + common input
Manual reset, inverse input
Manual reset, + common input
Input type
+ common
+ common
+ common
+ common
Inverse
Inverse
Inverse
Inverse
---
Rated voltage
24 VAC/VDC
24 VDC
24 VAC/VDC
CSM_G9SB_DS_E_2_1
G9SB-2002-A
G9SB-2002-C
G9SB-3012-A
G9SB-3012-C
G9SB-3010 *
G9SB-200-B
G9SB-200-D
G9SB-301-B
G9SB-301-D
Model
1

Related parts for G9SB-3012-A

G9SB-3012-A Summary of contents

Page 1

... Manual reset, + common input Reset mode Input type 2 channels Inverse Auto-reset + common 2 channels Inverse Manual reset + common None Auto-reset 2 channels Inverse + common 2 channels Inverse Manual reset + common CSM_G9SB_DS_E_2_1 Rated voltage Model G9SB-2002-A G9SB-200-B 24 VAC/VDC G9SB-2002-C G9SB-200-D --- 24 VDC G9SB-3010 * G9SB-3012-A G9SB-301-B 24 VAC/VDC G9SB-3012-C G9SB-301-D 1 ...

Page 2

... VAC/VDC: 24 VAC, 50/60 Hz, or 24VDC 24 VDC: 24 VDC 85% to 110% of rated power supply voltage 1.7 W max. G9SB-3010 60 mA max. * G9SB-3010 Resistive load 250 VAC VDC G9SB-200@-@ G9SB-3010 2 2 Approx. 135 g G9SB G9SB-301@-@ 2.0 VA/1.7 W max. G9SB-301@-@ 30 mA max. G9SB-301@-@ G9SB-301@-@ Approx. 120 g 2 ...

Page 3

... With G9SB-@@@2-A/C, 1-channel input wiring is not possible. *2. Output Contacts G9SB-2002-A/C: Safety Output Contacts 13-14, 23-24. G9SB-3012-A/C: Safety Output Contacts 13-14, 23-24, 33-34. Auxiliary Contact 41-42. G9SB-200-B/D: Safety Output Contacts 13-14, 23-24. G9SB-301-B/D: Safety Output Contacts 13-14, 23-24, 33-34. Auxiliary Contact 41-42. ...

Page 4

... G9SB-301-@-@ 83 18 2.5 100 max × 112 max. 18 max. (Average: 17.5) 3 × 112 max. 23 max. (Average: 22.5) G9SB (Unit: mm) Terminal Arrangement G9SB-3010 G9SB-200@-@ 13 23 T31 T11 T12 A1 41 T31 A1 PWR PWR (green) (green (orange) (orange (orange) (orange) T21 T22 A2 42 T32 A2 2 ...

Page 5

... Application Examples G9SB-2002-A (24 VAC/VDC) or G9SB-3012-A (24 VAC/VDC) with 2-channel Limit Switch Input/Auto-reset Open A1 A2 T11 T12 T31 + - Control SA circuit T21 T22 Note: 1. External connections and timing charts for G9SB-200-B/301-B models are the same as those for G9SB-2002-A/3012-A models. 2. This circuit conforms to Safety Category 4. ...

Page 6

... G9SB-200-D (24 VAC/VDC) or G9SB-301-D (24 VAC/VDC) with 2-channel Safety Sensor/Manual Reset Emitter RS-485(A) (Gray) RS-485(B) (Pink T21 + - TH SA Note: This circuit conforms to Safety Category 4. *1. Only the G9SB-301-D model has terminals 33-34 and 41-42. *2. Wiring is shown for when the F3SJ-A auxiliary output turns ON for light interruption. ...

Page 7

... G9SB-3010 (24 VDC) with 2-channel Limit Switch Input/Auto-reset Open A1 A2 T31 T32 + - Control SA circuit Note: This circuit conforms to Safety Category 3. Timing Chart Limit switches S1 and S2 K1 and K2 (NC) KM1 K1 and K2 (NO) KM2 KM1 and KM2 (NC) Feedback loop KM1 and KM2 (NO KM1 KM2 ...

Page 8

... Stranded wire: 0 Solid wire: 0.2 to 2.5 mm • Tighten each screw to a torque of 0.5 to 0.6 N·m, or the G9SB may malfunction or generate heat. • External inputs connected to T11 and T12 or T21 and T22 of the G9SB must be no-voltage contact inputs. • Strip the wires max. ...

Page 9

... Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS ...