NT31C-ST143-EV3 Omron, NT31C-ST143-EV3 Datasheet - Page 75

no-image

NT31C-ST143-EV3

Manufacturer Part Number
NT31C-ST143-EV3
Description
5.7 8-Color Dsp,STN,Ivory,Eng
Manufacturer
Omron
Datasheet

Specifications of NT31C-ST143-EV3

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Connecting to the RS-232C Port at the Host
58
Setting the Switches of a CPM2C
When using a CPM2C, the switches on the front panel must be set as shown
below in order to make the PLC Setup settings effective.
Setting the Switches on an RS-232C Adapter
When using a CPM1-CIF01 RS-232C Adapter, set the mode switch as shown
in the following diagram.
CS/CJ-series CPU Unit: CS1G/H-CPU@@-E(V1), CS1G/H/D-CPU@@H-E,
CJ1G/M-CPU@@, CJ1G/H-CPU@@H
Connect to the built-in RS-232C port of the CPU Unit, or the RS-232C port of
the Communications Board. Note that the connection to a peripheral port
must be made via an RS-232C Adapter (CS1W-CN118) specially designed
for connecting to a peripheral port.
PLC Setup
When connecting to a CS/CJ-series CPU Unit, set the following communica-
tions conditions for the PLC Setup area. Since the settings shown below are
the PLC default settings for the CPU Unit, no change to the PLC Setup is nec-
essary as long as the communications speed is maintained at 9600 bps.
*1
Set the mode setting switch to HOST (upper position).
Communications speed
Stop bits
Parity
Data length
Unit No. for the host link
Set the host link communications speed at 9600 bps or 19200 bps with the
memory switch at the NT31/NT31C. For details, refer to 6-7-2 Setting the
Host Link Method (page 161). When the communications speed is set to
19200 bps, the PLC Setup of the CPU Unit need to be changed.
Item
The settings for SW1 and SW2 depend upon the usage of the
peripheral port and RS-232C port.
• Connecting PT to peripheral port
• Connecting PT to built-in RS-232C port
• Connecting PT to built-in RS-232C port
(A device that requires non-standard communications
settings is connected to the peripheral port.)
(A Programming Console is connected to the peripheral port.)
Set the same speed as set at the NT31/NT31C(*1)
2 stop bits
Even
ASCII 7 bits
00
Setting at Host
SW1: OFF
SW2: ON
SW1: OFF
SW2: OFF
CPM1-
CIF01
CPM1
Section 4-1

Related parts for NT31C-ST143-EV3