BF-1 Omron, BF-1 Datasheet - Page 28

ELECTRODE HOLDER

BF-1

Manufacturer Part Number
BF-1
Description
ELECTRODE HOLDER
Manufacturer
Omron
Datasheet

Specifications of BF-1

Description/function
General and industrial use electrode holder
Equipment Type
Electrode Holder
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
61F-GjP
61F-G1P
Application 2: Automatic Water Supply Control with Abnormal Water Shortage Alarm
Note: Be sure to ground terminal 15.
Water supply
Pump OFF
200-VAC power supply
Pump ON
B
MCCB
Shortage
THR
P
L
R S T
Water tank
E
1
E
2
E
4
E
Electromagnetic switch
3
M
Water drainage
P
A
61F-G1P
Water supply
source
8
Transformer
200 V
7
0 V
Water tank
9
14
*
U
15
24 V
24 V
2
8 V
6
Control
circuit
Control
circuit
E
3
10
5
B
E
U
4
1
Alarm
2
12
U
E
U
2
2
1
E
The pump stops when the water level reaches E1 and starts
when the water level drops below E2.
If the water level drops below E4 for any reason, the pump stops
and the alarm sounds.
Insert a pushbutton switch (NO contact) between 11 and 15.
When starting the pump and after recovering from a power
failure, if the water level has not yet reached E4, press the
pushbutton switch to start the pump by short-circuiting E3 and
E4.
If the pump stops upon release of the pushbutton switch, keep
pressing the pushbutton switch.
1
U
Pushbutton switch
11
PS-4S
1
4
U
2
1
3
61F-GjP

Related parts for BF-1