Top/Valley Hold
Setting Using the DeviceNet Configurator
Temperature Input Terminals
1,2,3...
Note
Top/valley hold is used to hold the top and valley values of the temperature
input value.
Temperature values that fluctuate more than twice the hysteresis value are
monitored, and the top or valley values are held. The top or valley value is
allocated along with the Top/Valley Detection Timing Flags, which can be
used to check the hold timing.
When the Hold Flag (output) allocated in the OUT Area turns ON, the hold
function starts, refreshing the top or valley value until the Hold Flag turns OFF.
(The last value is held when the Hold Flag turns OFF, but the next time the
Hold Flag turns ON, the hold value is initialized as soon as a top or valley
occurs.) The comparator can be used to compare the top or valley value allo-
cated as temperature data 1. (Refer to details on the comparator function.)
Example of Valley Hold
1. A delay in network transmission time will occur from the time the Hold Flag
2. The time that the Top/Valley Detection Timing Flags are ON can be adjust-
3. If the Hold Flag turns OFF during the time the Top/Valley Detection Timing
1. Double-click the icon of the Temperature Input Terminal to be set in the
Top/Valley Detection
Timing Flag
Hold value
Hold Flag
turns ON (or OFF) in the Master’s ladder program until notification of the
flag’s status is actually sent to the Slave. Therefore, even when the Hold
Flag is ON, the first temperature data transmitted to the Master when the
CPU Unit power is turned ON may be the data from when the Hold Flag
was OFF. To collect top/valley hold data using the Hold Flag at the Master,
configure a ladder program which considers the transmission delay time
when the Hold Flag is turned ON, then enables the top/valley hold values
after a fixed time interval.
ed by setting the one-shot time. Use the Configurator to set the one-shot
time (the setting range is 1 to 65,535 ms).
Flag is set to be ON, both flags will turn OFF simultaneously.
Main Window and open the Edit Device Parameters Window. (From the
Maintenance Mode Window, click the right mouse button over the Slave
icon and select Parameters and Edit.)
Hold function
starts.
One-shot time
Temperature
input value
Valley hold
value
Section 7-6
Hold function
stops.
Last value
is held.
411
Related parts for DRT2-OD32BV-1
Image
Part Number
Description
Manufacturer
Datasheet
Request
R
Part Number:
Description:
DRT2 Mix IO E-Con 8in/out PNP
Manufacturer:
Omron
Datasheet:
Part Number:
Description:
DRT2 16 OutMIL Conn Cable With
Manufacturer:
Omron
Datasheet:
Part Number:
Description:
DRT2 16 In MIL Connector NPN
Manufacturer:
Omron
Datasheet:
Part Number:
Description:
DRT2 16 In MIL Connector PNP
Manufacturer:
Omron
Datasheet:
Part Number:
Description:
DRT2 16 In MIL Conn Cable With
Manufacturer:
Omron
Datasheet:
Part Number:
Description:
DRT2 16 In MIL Conn Cable With
Manufacturer:
Omron
Datasheet:
Part Number:
Description:
DRT2 Mix IO E-Con8 In/out, NPN
Manufacturer:
Omron
Datasheet:
Part Number:
Description:
DRT2 8 Out TermOutal NPN
Manufacturer:
Omron
Datasheet:
Part Number:
Description:
G6S-2GLow Signal Relay
Manufacturer:
Omron Corporation
Datasheet:
Part Number:
Description:
Compact, Low-cost, SSR Switching 5 to 20 A
Manufacturer:
Omron Corporation
Datasheet:
Part Number:
Description:
Manufacturer:
Omron Corporation
Datasheet: