PAXLIT00 Red Lion Controls, PAXLIT00 Datasheet - Page 6

METER AC CURRENT 5A 3 1/2-DIGIT

PAXLIT00

Manufacturer Part Number
PAXLIT00
Description
METER AC CURRENT 5A 3 1/2-DIGIT
Manufacturer
Red Lion Controls
Series
PAX®LITEr
Type
Ammeterr
Datasheets

Specifications of PAXLIT00

Measuring Range
0 ~ 5A
Display Style
Red Characters, Black Background
Display Type
LED
Display Face Size
3.80" L x 1.95" W (96.5 x 49.5mm)
Display Digits
3.5
Display Digits - Height
0.560" (14.22mm)
Backlight
Without
Mounting Type
Panel Mount
Termination
Terminal Block
Voltage - Supply
115VAC,230 VAC
No. Of Digits / Alpha
3-1/2
Meter Function
AC Ammeter
Meter Range
0A To 5A
Digit Height
14.2mm
Power Consumption
6VA
Operating Temperature Range
0°C To +60°C
Supply Voltage Ac, Min
115V
Accuracy
±0.5% %
Connection Type
Cage-Clamp
Cut Out, Panel
3.62×1.77 "
Dimensions
4.2"L×3.8"W×1.95"H
Display Digit Height
0.56 "
Display Resolution
2.5 mA
Function
Ammeter
Meter Type
AC Current
Number Of Digits
3-1/2
Primary Type
Electronic
Range, Measurement
0 to 5 A
Special Features
Multi-Range Unit
Standards
cULus Listed, CE Marked
Temperature, Operating
0 to 60 °C
Voltage, Supply
115/230 VAC
Weight
0.65 lbs
Character Size
0.56"
Display Font Color
Red
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
RLC109
MOTOR
CURRENT TRANSFORMER
the “COMM.” (Terminal 3) and the “5AMP” (Terminal 4) to the external
current transformer. The current carrying wire to be sensed is passed through the
center of the current transformer. The resolution of the display, in this case, is
0.1 Amp, therefore, “Switch #1” is selected.
portable digital current meter capable of measuring the motor current. Scaling
will be accomplished by adjusting the scaling pot on the PAXLIT meter to agree
with the portable digital current meter. The operator turns on the AC motor and
lifts a large weight to load the motor. The installer then simply adjusts the
scaling adjustment, located at the rear of the unit, until the display is equal to
the value indicated on the portable current meter. The meter will now indicate
the load current of the motor precisely.
signal to a desired display value is performed by enabling the scale pot
DIP switch. If the meter appears to be indicating incorrectly or inaccurately,
refer to Troubleshooting before attempting to calibrate the meter.
performed by qualified technicians using appropriate equipment.
6.0 T
5.0 A
7.0 C
PROBLEM
NO DISPLAY
INCORRECT DISPLAY
OVER-RANGE INDICATION
The PAXLIT 5 Amp AC Current Meter is configured by simply connecting
The meter is now ready to be scaled. The installer has access to a calibrated
The meter has been fully calibrated at the factory. Scaling to convert the input
When recalibration is required (generally every two years), it should only be
CAUTION: It is recommended that the current transformer be
internally protected or that a voltage clamping circuit be provided,
preventing dangerous high voltage across the CT secondary
windings in case of accidental opening of the secondary output
leads when the primary is energized.
according to local NEC regulations for installation of current
instrument transformers.
CURRENT
In order to prevent risk of electric shock ensure CT is installed
ROUBLESHOOTING
PPLICATION
ALIBRATION
For further assistance, contact technical support at the appropriate company numbers listed.
MEASUREMENT
USING
REMEDIES
CHECK: Power switch and line voltage
CHECK: Scaling adjustment pot DIP switch position
ADJUST: Scaling pot
VERIFY: Input Signal
VERIFY: Input signal
A
6
Input Calibration
Allow a 30 minute warm-up period before calibrating the meter.
1. Set the DIP switch off to disable the scaling pot.
2. Apply half scale input signal.
3. Adjust calibration potentiometer as necessary for the display to read 1000
4. Apply zero signal and ensure display reads zero.
5. Apply full scale signal and ensure display reads 1999.
Before starting, verfiy that the precision signal source is connected and ready.
Then perform the following procedure:
(ignore decimal point)
WARNING: Calibration of this meter requires a signal source
with an accuracy of 0.05% or better and an external meter with
an accuracy of 0.005% or better.
115V/230V
1
2
3
4
5 6
CURRENT TRANSFORMER
200 AMP/5 AMP RATIO
7
8
9
10
CRANE
MOTOR
AC
ADJUST
SCALE