PAXLCL00 Red Lion Controls, PAXLCL00 Datasheet

METER CURRENT LOOP 3 1/2-DIGIT

PAXLCL00

Manufacturer Part Number
PAXLCL00
Description
METER CURRENT LOOP 3 1/2-DIGIT
Manufacturer
Red Lion Controls
Series
PAX®LITEr
Type
Process Meter (4-20mA Loop)r
Datasheets

Specifications of PAXLCL00

Measuring Range
4-20mA Loop
Display Style
Red Characters, Black Background
Display Type
LED
Display Face Size
3.80" L x 1.95" W (96.5 x 49.5mm)
Display Digits
3.5
Display Digits - Height
0.560" (14.22mm)
Backlight
Without
Mounting Type
Panel Mount
Termination
Terminal Block
Voltage - Supply
85 V ~ 250 VAC
No. Of Digits / Alpha
3-1/2
Meter Function
Loop Current
Meter Range
4mA To 20mA / 10mA To 50mA
Digit Height
14.2mm
Power Consumption
6VA
Operating Temperature Range
0°C To +60°C
Supply Voltage Ac, Min
85V
Accuracy
±0.05% %
Connection Type
Cage-Clamp
Cut Out, Panel
3.62×1.77 "
Dimensions
4.2"L×3.8"W×1.95"H
Display Digit Height
0.56 "
Function
Ammeter
Number Of Digits
3-1/2
Primary Type
Electronic
Range, Measurement
4 to 20/10 to 50 mA
Special Features
Multi-Range Unit
Standards
cULus Listed, CE Marked
Temperature, Operating
0 to 60 °C
Time, Response
1 Second to settle for step change
Voltage, Supply
85 to 250 VAC
Weight
0.65 lbs
Character Size
0.56"
Rohs Compliant
NA
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
na, Lead free / RoHS Compliant
Other names
RLC112
Tel +1 (717) 767-6511
Fax +1 (717) 764-0839
www.redlion.net
MODEL PAXLCL - PAX LITE CURRENT LOOP METER
GENERAL DESCRIPTION
measurement of process variables. With its high sensitivity and programmability,
the PAX Lite Current Loop Meter can be set up for a wide variety of applications.
In most plants the PAXLCL can be used for 90 to 95% of current loop meter needs
for readout of pressure, flow, temperature, level and other variables. The meter has
been specifically designed for harsh industrial environments. With NEMA 4X/
IP65 sealed bezel and extensive testing of noise effects to CE requirements, the
meter provides a tough yet reliable application solution. This allows the PAXLCL
to be used in dirty, hostile environments and in wash-down areas. The 3 1/2-digit
bi-polar display (minus sign displayed when current or voltage is negative)
features 0.56" (14.2 mm) high, 7-segment LEDs for easy reading.
C C
DIMENSIONS In inches (mm)
The premium features of the PAX Lite Series can now be applied to
U L
R
US LISTED
US LISTED
(96.5)
3.80
IND. CONT. EQ.
51EB
mA
(49.5)
1.95
(2.5)
.10
Note: Recommended minimum clearance (behind the panel) for mounting clip installation is
2.1" (53.4) H x 5.0" (127) W.
(104.1)
4.10
1
SAFETY SUMMARY
literature or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
*
All safety related regulations, local codes and instructions that appear in the
Also adapts to 0 to 50, 0 to 20, 0 to 10, 1 to 5 mA ranges as well as
bi-polar inputs.
DUAL RANGE, 4 to 20 mA or 10 to 50 mA *
3 1/2-DIGIT, 0.56" (14.2 mm) HIGH RED LED READOUT
24 VDC EXCITATION SUPPLY
WIDE SPAN & OFFSET SCALING RANGE
OVER-RANGE INDICATION
SELECTABLE DECIMAL POINTS
NEMA 4X/IP65 SEALED FRONT BEZEL
OPTIONAL CUSTOM UNITS OVERLAY W/BACKLIGHT
instructions prior to installation
and operation of the unit.
CAUTION: Read complete
(44.5)
1.75
1 2 3 4
5 6
3.60 (91.4)
7
8 9 10 11
CAUTION: Risk of electric shock.
Bulletin No. PAXLCL-D
Drawing No. LP0567
Released 11/09
(44.5)
1.75

PAXLCL00 Summary of contents

Page 1

Tel +1 (717) 767-6511 Fax +1 (717) 764-0839 www.redlion.net MODEL PAXLCL - PAX LITE CURRENT LOOP METER LISTED US LISTED R IND. CONT. EQ. 51EB GENERAL DESCRIPTION The premium features of the PAX Lite Series ...

Page 2

ABLE F ONTENTS Ordering Information . . . . . . . . . . . . . . . . . . . . 2 General Meter Specifications . . . . . . . . ...

Page 3

G M ENERAL ETER 1. DISPLAY: 3 1/2-digit, 0.56" (14.2 mm) high, 7-segment red LED, (-) minus sign displayed when current or voltage is negative. Decimal points inserted before 1st, 2nd, or 3rd least significant digits by DIP switch selection. ...

Page 4

I NSTALLING THE Installation The PAX meets NEMA 4X/IP65 requirements when properly installed. The unit is intended to be mounted into an enclosed panel. Prepare the panel cutout to the dimensions shown. Remove the panel latch from the unit. ...

Page 5

EMC INSTALLATION GUIDELINES Although this meter is designed with a high degree of immunity to Electro- Magnetic Interference (EMI), proper installation and wiring methods must be followed to ensure compatibility in each application. The type of the electrical noise, its ...

Page 6

S CALING THE BUFFER AMP V V -LOOP (-) 4-20MA RANGE -LOOP CURRENT 4 SHUNT SPAN=150 (-) RESISTORS 10-50MA RANGE SPAN=0 (+) +LOOP 3 INPUT SIGNAL SCALING CIRCUIT DESCRIPTION OF OPERATION The PAX Lite Current ...

Page 7

... The Company disclaims all liability for any affirmation, promise or representation with respect to the products. The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries, deaths, property ...

Page 8

... Ahmedabad-382480 Gujarat, India Tel +91 987 954 0503 Fax +91 79 275 31 350 +1500 SPAN NULL A (-) OFFSET C -1500 India Building 13, No.99 Tianzhou Road ShangHai, P.R. China 200223 D CHECK B CURRENT (+) CHECK Red Lion Controls China Unit 101, XinAn Plaza Tel +86 21 6113-3688 Fax +86 21 6113-3683 ...