SDV-DM7 AC200/220 Omron, SDV-DM7 AC200/220 Datasheet - Page 75

no-image

SDV-DM7 AC200/220

Manufacturer Part Number
SDV-DM7 AC200/220
Description
Sensor Hardware & Accessories VOLTAGE SENSOR
Manufacturer
Omron
Datasheets

Specifications of SDV-DM7 AC200/220

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Single-function Models with Timing Function
Note: SDV-FL and SDV-FM models can also be equipped with the timing function as a special specification. Ask your OMRON representative for
Specifications
Single-function Models
Overvoltage or Undervoltage Detection (Switch Selectable)
Note: Ripple is 5% max. with DC power supplies.
Dual-function Models
Overvoltage and Undervoltage Detection
Note: 1. Inquire about production of models with 120- and 240-VAC control power supply.
12 VDC
24 VDC
48 VDC
100/110 VDC
125 VDC
200/220 VDC
100/110 VAC
120 VAC
200/220 VAC
240 VAC
SDV-FL@
SDV-FM@
SDV-FH@
SDV-FH@T
SDV-DM@
SDV-DH@
Control power supply voltage
Model
Model
details.
2. The ripple factor must be 5% or less for DC power supplies.
DC or AC
(selectable)
Input voltage
DC
DC or AC
(selectable)
Input voltage
0.2 to 12 V
10 to 300 V
4 to 240 mV
(4 to 12 mV, 10 to 30 mV,
20 to 60 mV, 40 to 120 mV,
80 to 240 mV)
0.2 to 12 V
(0.2 to 0.6 V, 0.5 to 1.5 V, 1 to 3 V,
2 to 6 V, 4 to 12 V)
10 to 300 V
(10 to 30 V, 25 to 75 V, 50 to 150 V,
100 to 300 V)
Intermediate voltage of
SDV-FH1T
SDV-FH2T
SDV-FH3T
SDV-FH4T
SDV-FH5T
SDV-FH51T
SDV-FH6T
SDV-FH61T
SDV-FH7T
SDV-FH71T
Selectable operating range
Selectable operating range
dead band
0.2 to 0.6 V
0.5 to 1.5 V
1 to 3 V
2 to 6 V
4 to 12 V
10 to 30 V
25 to 75 V
50 to 150 V
100 to 300 V
ON-delay
Input: DC or AC (selectable); input voltage range: 10 to 300 V
0.02 to 0.1 V
0.05 to 0.25 V
0.1 to 0.5 V
0.2 to 1 V
0.4 to 2 V
1 to 5 V
2.5 to 12.5 V
5 to 25 V
10 to 50 V
Dead band
voltage
2% to 30% (related to
operating value)
Selectable reset value range
Operating mode
Overvoltage:
(Intermediate voltage of
dead band + dead band
voltage) – (dead band volt-
age x 2/3) min.
Undervoltage:
(Intermediate voltage of
dead band – dead band
voltage) + (dead band volt-
age x 2/3) max.
OFF-delay
Reset value
Voltage Sensor
12, 24, 48, 100/110, 125, 200/
220 VDC (see note);
100/110, 200/220/240 VAC
(50/60 Hz)
12, 24, 48, 100/110, 125 VDC;
100/110, 200/220/240 VAC
(50/60 Hz)
Control power supply
Control power supply
Startup lock
SDV
73