K2CU-F80A-C AC32-80A AC100 Omron, K2CU-F80A-C AC32-80A AC100 Datasheet - Page 13

no-image

K2CU-F80A-C AC32-80A AC100

Manufacturer Part Number
K2CU-F80A-C AC32-80A AC100
Description
Detector Switches Heater Fault Detector
Manufacturer
Omron
Datasheet

Specifications of K2CU-F80A-C AC32-80A AC100

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
K2CU
General
Refer to “External Connections” before using the K2CU with exter-
nal CTs.
When a temperature controller is used in combination with the
K2CU (except for the K2CU-FjjA-jGS), the heater element(s)
must be turned ON or OFF for 1 s or longer (although the heater ele-
ment(s) can be turned ON for 0.5 s according to the specifications).
The K2CU cannot be used with a phase-control circuit, inverter cir-
cuit, frequency-count circuit, cycle-control unit, or a motor load.
Mounting
Securely mount the K2CU as horizontally as possible although
there is no particular limitation of mounting directions.
Operating Current Setting when Several Heaters are Used
The following table shows relative values of changes in the current
when any one of several heaters connected in parallel has burned
out. The current value under normal condition is 1. Use this table as
a guideline in determining the operating current.
Note: 1. This table shows the respective change rates in current when any one of several heaters connected in parallel has burned out.
2. The current value under the normal condition is 1.
3. The values in this table are logical values. Actually, these values may vary slightly because of influence of unbalanced loads (heat-
ers). It is therefore recommended to test the actual current values and the load condition before determining the operating current,
especially when the current under the normal condition and that under an abnormal condition do not significantly differ.
I
I
I
No. of heater
per phase = n
No. of heater = n
No. of heater
per phase = n
Connection
Current in burned-out phase
Current in other phases
Current in burned-out phase
Current in other phases
Connection
Solderless-type terminal must be connected to the terminals se-
curely.
Wire the terminals correctly by referring to the external connections.
The terminals have no polarity. Be sure to connect 100 (or 110) V to
the 100-V (or 110-V) terminals and 200 (or 220) V to the 200-V (or
220-V) terminals of the K2CU-P or the K2CU-P may malfunction.
The control power source for the K2CU (except for the
K2CU-FjjA-jGS) must be supplied from the load side via a con-
tactor.
Be sure to impose a voltage between the 0-V terminal and 100-V (or
110-V) terminal or the 0-V terminal and 200-V (or 220-V) terminal of
the K2CU-P, otherwise the K2CU-P will not operate.
0
0
0.87
0.58
1
n = 1
0.5
0.6
0.92
0.77
1
n = 2
0.67
0.75
0.95
0.84
1
n = 3
0.75
0.82
0.96
0.88
1
n = 4
0.8
0.86
0.97
0.91
1
K2CU
n = 5
13

Related parts for K2CU-F80A-C AC32-80A AC100