K2CU-F80A-C AC32-80A AC100 Omron, K2CU-F80A-C AC32-80A AC100 Datasheet - Page 5

no-image

K2CU-F80A-C AC32-80A AC100

Manufacturer Part Number
K2CU-F80A-C AC32-80A AC100
Description
Detector Switches Heater Fault Detector
Manufacturer
Omron
Datasheet

Specifications of K2CU-F80A-C AC32-80A AC100

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
K2CU
Use the potentiometer on the front panel to set the operating cur-
rent.
Rotate the knob to set the desired current value at which the Heater
Burnout Detector should operate. Do not exceed the maximum and
minimum positions.
The K2CU-F’s scale is divided into 12 graduations including sub-
graduations and the K2CU-P’s scale is divided into 5 graduations.
The knobs of the K2CU-F and K2CU-P as shown in the illustrations
are set to 32 A and 0.7 A respectively.
The following table shows the different connections possible. The formula under each illustration indicates the electrical current value of the
heater elements under normal and abnormal conditions.
Note: Values in this table are correct when a 200 VAC, 1 kW heater is used on a single-phase or three-phase current.
Single phase
Three
phase
Setting of Operating Current
Heater Connection and Current
Phase
Delta
network
Star
network
V
network
200 V
200 V
200 V
200 V
200 V
200 V
200 V
200 V
200 V
200 V
Normal condition
5 A
(5 A x
(5 A x
8.7 A
8.7 A
8.7 A
2.9 A
2.9 A
2.9 A
5 A
8.7 A
5 A
(5 A x
3
= 8.7 A)
5 A
1 kW
1
3
) 3
)
1 kW
1 kW
1 kW
1 kW
1 kW
1 kW
1 kW
1 kW
Knob
(5 A x
(5 A x
The set operating current is defined as the mean value of the heater
current under normal operating conditions and the heater current
under a burnout or abnormal condition.
7.5 A
7.5 A
2.5 A
2.5 A
2.5 A
2.5 A
1
3
3
x
x
(5A x 1/2)
2
3
2
Set value =
3
)
)
200 V
Abnormal condition
0 A
Normal current + abnormal current
0 A
Red point
(indicates the set value)
2
5 A
8.7 A
5 A
5 A
5 A
2.5 A
2.5 A
(5 A x
(5 A x
(5A x 1)
1
3
3
x
x
2
1
3
3
)
)
K2CU
5