30
Easier Design of Machine Error Screens
You can easily make a machine
troubleshooter without making
similar error screens.
Individual error screens that were
previously made for each error can
now be integrated into one. It is
possible to switch only the error
details (text and screen) without
ladder programming in conjunction
with the alarm bit.
Easy-to-Use Multifunction Objects
Multiple functions can be
executed on-screen with one
button without macros.
Multifunction Objects combine the
functions of multiple objects into one
object. Multiple functions can be
executed by pressing one button
without using troublesome macros.
Setup is easy. For example, a setting
can be made on-screen using the
Support Software to turn ON a bit to
start a machine, set a value, and then
change the screen.
Multifunction Objects support
four safety functions.
Switches that do not immediately
operate when touched can be easily
made without ladder programming.
Plenty of Basic Functions
With this system, this frame is shared, and
the error details in the pink frames are switched
with an alarm or other item as the trigger.
For example, in conjunction with
an alarm bit (See note.)
Note: Alarms, PLC/PT memory, and other
Easy On-screen Setup with Support
Software!
Alarm bit 10.02 ON (printing error)
pressing prohibited
Double-press
Alarm bit 10.01 ON (no paper)
items can be selected for the
switching trigger.
ON delay
Simultaneous
OFF delay
Time the button is pressed.
Turns ON when the button is pressed for at least a specified time.
Turns ON when the button is pressed twice within the specified time.
Does not turn ON when the button is pressed at the same time as another button.
Turns OFF after a specified time lapses after the button is released.
Button
pressed
Relay
status
Button
pressed
Relay
status
Button
pressed
Relay
status
Execute multiple
functions with
one button.
Text selection
Multifunction execution
with one object
Delay: 0.5 to 15 s
Acceptance time:
0.5 to 30 s
Delay: 0.5 to 15 s
Image selection
ON!
Example:
The bit turns ON.
The word is set.
The screen
changes.
ON!
ON!
Plentiful Graphing Functions
[Trend Graph (Data Log) Function]
Logging data is stored as a CSV file in the
Memory Card mounted in the NS-series PT. The
data stored in the Memory Card can be read or
deleted from the screen.
A log can be saved automatically, without any programming, just by selecting the Save the data periodically Option
in the Data Log Setting Window.
[Line Graph Function]
The data logged by the PLC can be displayed in overlapping graphs, so a device's operation can be compared for
evaluation and analysis. In addition, up to 1,000 words of consecutive data can be displayed as a line graph, data can be
displayed together, and any region can be magnified.
(1) Graphs can be superimposed.
[Continuous Line Function]
A graph can be plotted in any position
by specifying the X and Y coordinates
of the vertices. Also, the graph can be
moved on the screen by specifying the
movements from the PLC.
A device's operation is easier to understand when presented visually.
A variety of graphing functions are built into the PTs, such as the trend graph, which can log data over a long
term, and the line graph, which can display overlapping graphs. A device's operation is easier to understand when
presented visually.
Long-term data logging and storage are
also easily achieved.
The earlier line graph function as been further improved.
Any position from the host (PLC) can be plotted as a graph.
Auto-
matically
saved
Logging data for each day
(43,200 points) is saved in
the Memory Card in CSV
format.
Memory
Card
D0000
D0001
D0002
(2) The display can be magnified.
LOG001.CSV 04/06/04 10:00
LOG002.CSV 04/06/05 10:00
LOG003.CSV 04/06/06 10:00
LOG004.CSV 04/06/07 10:00
LOG005.CSV 04/06/08 10:00
LOG006.CSV 04/06/09 10:00
LOG007.CSV 04/06/10 10:00
PLC
X1
Y1
X2
Y2
X3
Y3
Suffixes are automatically
added to file names set in
the CX-Designer.
Read file button
Y
Information in the PLC's format can be plotted
moment-by-moment.
(X1, Y1)
(X2, Y2)
It is possible to make a one-week
log by automatically saving the
data seven times.
(X3, Y3)
The log data files in the
Memory Card appear as
shown below when the read
file button is pressed.
X