Safety Control Relay HR1S-AF
•
•
•
•
•
•
•
•
Part Numbers
Specifications
Note: Short-circuit of S11 and S21 activates the overcurrent protection circuit,
interrupting the power supply. The safety output turns off.
Normal status is restored when the short-circuit is removed.
Use a 4A fuse (Type gL) for power line protection.
Use a 4A fuse (Type gL) or a 6A fast blow fuse for output line protection.
Part Numbers
HR1S-AF5130B
HR1S-AF5130PB
Operating Temperature
Degree of Protection
Rated Power Voltage
Power Consumption
Overcurrent Protection
Control Circuit Voltage
Performance Level (PL)
Safety Category
Safety Integrity Level (SIL)
Response Time
Input Synchronization Time
Overvoltage Category
Pollution Degree
Rated Insulation Voltage
Maximum Input Resistance
Safety
Outputs
Output
Contact
Ratings
Operation Frequency
Rated Current
Wire Size
Weight
2NC safety input type, such as E-Stops or Interlock Switches
EN ISO 13849-1 PLe, Safety Cat 4 compliant, and EN 62061 SIL 3
Welding detection of start switch
Fault diagnosis function with dual safety circuits.
Internal relay operations can be moni tored with LED Indicator.
Finger-safe protection
22.5mm wide, 35mm DIN rail mounting
UL listed, CSA certified, TÜV NORD approved
Instantaneous
(Stop Cat 0)
Safety
Circuit
Minimum
Applicable Load
AC-15
DC-13
Terminal Style
Integrated Terminal Block
Removable Terminal Block
–25 to +55°C (no freezing)
Terminal: IP20, Housing: IP40
24V AC (–15 to +10%) 50/60 Hz
24V DC (–15 to +10%)
5 VA maximum (24V AC)
2.5W maximum (24V DC)
Electronic (Note)
24V
e (EN ISO 13849-1)
4 (EN ISO 13849-1)
3 (EN 62061)
When S11-S12, S21-S22 are interrupted:
20 ms maximum
When power is interrupted: 60 ms maximum
Unlimited
III
2
300V
90Ω
3NO
C300: Ue= 240VAC, Ie=0.75A
Ue=24VDC, Ie=2A
17V/10mA (initial value)
1200 operations/h maximum
Safety circuit output total: 18A maximum
Each safety circuit output: 6A maximum
HR1S-AF5130B:
HR1S-AF5130PB:
250g
1 × 2.5 mm
1 × 2.5 mm
2
2
, 2 × 0.75 mm
, 2 × 1.5 mm
2
2
maximum
maximum
Dimensions (mm)
LED Indicator
•
•
•
22.5
A1/A2 Fuse:
Turns on when power circuit is normal.
Turns off when power is interrupted or the electronic fuse blows.
K1: Turns on when K1 relay operates.
K2: Turns on when K2 relay operates.
A1/A2
Fuse
K1
K2
The HR1S-AF5130PB terminal block can
be removed and installed as shown,
allowing for easy installation and replace-
ment of modules.
114
Terminal Arrangement