ES-FL-2A BANNER ENGINEERING, ES-FL-2A Datasheet - Page 5

20H6269

ES-FL-2A

Manufacturer Part Number
ES-FL-2A
Description
20H6269
Manufacturer
BANNER ENGINEERING
Datasheet

Specifications of ES-FL-2A

Coil Voltage Vac Nom
24V
Coil Voltage Vdc Nom
24V
Contact Current Max
4A
Contact Voltage Ac Nom
250V
Contact Voltage Dc Nom
250V
Contact Configuration
DPDT-NC
No. Of Poles
2
Figure 2. Hookup of ES-FL-2A Emergency Stop Monitoring Safety Relay
Figure 3. Series Connection of Multiple Emergency Stop Switches
guided monitor contact of that relay must be added to the series feedback loop between safety relay terminals S33 and S34.
!
!
S23
24V ac/dc
S13
WARNING
stop control elements (MSC1 and MSC2). NEVER install suppressors directly across the output contacts of
the ES-FL-2A safety relay. It is possible for suppressors to fail as a short circuit. If installed directly across
the output contacts of the safety relay, a short-circuited suppressor will create an unsafe condition which
could result in serious injury or death.
WARNING
NEVER wire an intermediate device (for example, a programmable logic controller - PLC), other than a safety relay,
between ES-FL-2A safety relay outputs and the master stop control element it switches. To do so sacrifices the
control reliability of the control-to-machine interface, and creates an unsafe condition which could result in serious
injury or death. Whenever a safety relay is added as an intermediate switching device, a normally-closed forced-
A2
A1
(Reference ANSI B11.1 – 1988, Appendix B4)
If arc suppressors are used, they MUST be installed as shown across the actuator of the master
ES-FL-2A
MSC1
Monitor
Contact
S23
Emergency Stop Switch
S13
S33
S14
Reset Switch
S14
S24
S34
S24
MSC2
Monitor
Contact
4A max.
L2
L1
K1
K2
A
A
MSC1
13
14
Safety Relay
Redundant
Outputs
Internal
*
!
MSC2
23
24
E-Stop Safety Relay
K1
4A max.
K2
IMPORTANT
emergency stop switches,
individually, during each checkout
procedure.
B
B
*
*Arc suppressors
Master Stop
Control Elements
(see WARNING)
41
42
Monitor Contact
K3
Non-safety
Auxiliary
Check ALL
0.5A max.
page
5