A.c. Harmonic Filter
Manufacturer
Samwha Electric Co., Ltd.
Datasheet
Samwha
Samwha 28
Harmonic is commonly generated in electricity system due to devices using Thyristor.
It can causes electricity accidents and interference in the system
Therefore, the application of filter facilities is essential to prevent the effect
of Harmonic in the system and use electricity more efficiently.
Cyclic distortion wave is expressed as the sum of sine wave [50Hz], the integral number frequency and
major sine wave, integral number [50Hz] frequency.
This integral number frequency is called harmonic wave and according to the change of amplitude and
phase, wave form is changed resulting in synthetic distortion.
Combined distortion wave is manifested in distorted sine wave form. This form can be analyzed into
one fundamental wave [50Hz] which has random cycle and major sine wave which has integral number
frequency or subharmonic frequency.
If the frequency of it is higher than the fundamental frequency, it is called harmonics and if the
frequency of it is lower, it is called fractional harmonic wave or subharmonic.
For example, an distorted wave form comprising sine wave type [50Hz] and 5th [250Hz] and 7th [350Hz]
wave form is analyzed as following :
ex ) Harmonic = Fundamental Wave + 5th Harmonic Part + 7th Harmonic Part
•Thyristior controller
•Speed controller
•Low speed starter
•Power factor compensator
•Rectifier
•Arc furnace
•Transformer, Reactor
•Transformer, Reactor
• N on-linear loads such as rotating devices
changing the wave form of the current which
generates harmonics.
Application
What is harmonic
Harmonic Generator
Creative TEchnology Provider
=
4. Special Capacitor
+
• C ollecting data[system condition, harmonics
•Drawing system impedance map
• C alculating harmonics impedance and
• Harmonic flow calculation
•Simulation
• C hecking abnormal resonance in the system and
•Designing Switcher PNL, Structure
•Testing the operation after installation
•Test report
spectrum, THD limit]
determining filtering order
the possibility of harmonics extension
Process of Harmonic
Filter Engineering
+

Related parts for smfl-86150ks

smfl-86150ks Summary of contents

Page 1

Samwha Creative TEchnology Provider 4. Special Capacitor Application 〉 Harmonic is commonly generated in electricity system due to devices using Thyristor. It can causes electricity accidents and interference in the system Therefore, the application of filter facilities is essential to prevent the effect of Harmonic in the system and use electricity more efficiently. What is harmonic 〉 Cyclic distortion wave is expressed as the sum of sine wave [50Hz], the integral number frequency and major sine wave, integral number [50Hz] frequency. This integral number frequency is called harmonic wave and according to the change of amplitude and phase, wave form is changed resulting in synthetic distortion. Combined distortion wave is manifested in distorted sine wave form. This form can be analyzed into one fundamental wave [50Hz] which has random cycle and major sine wave which has integral number frequency or subharmonic frequency. If the frequency higher than the fundamental frequency called harmonics and if the frequency lower called fractional harmonic wave or subharmonic. For example, an distorted wave form comprising sine wave type [50Hz] and 5th [250Hz] and 7th [350Hz] wave form is analyzed as following : = ex ) Harmonic = Fundamental Wave + 5th Harmonic Part + 7th Harmonic Part Harmonic Generator 〉 •Thyristior controller ...

Page 2

A.C. Harmonic Filter Disturbance by Harmonics 〉 Once Harmonic is generated in system, it moves around and affects on the connected other electricity facilities. •Overheating and loss of transformer •Influx of over current of capacitor and noise •Instability of control system •Voltage change •Overload of rotator •Errors on the movement of circuit breaker •Impediment in communication and interfering OA functions •Heavy current in neutral and low voltage between phase and earthing What is Harmonic Filter? 〉 Harmonic filter is a device which represses and absorbs the outflow of harmonics generated in the electricity system. It consists of resistor, reactor and capacitor. Basic harmonic filter consists of lower order [5-13th order] single shunt filter which is synchronized with the harmonics current generated. For other higher order frequency, higher order filter shall be installed, if necessary. Effects of Harmonic Filter 〉 • I mprovement of power factor [invalid power in the electricity system is removed, resulting in the improvement of economics] ...

Page 3

Samwha Creative TEchnology Provider 4-1 A.C. Harmonic Filter Current Distortion Limits for General Distribution 〉 Systems [IEEE Std 519-199] Maximum Harmonic Current Distortion in Percent of I Individual Harmonic Order [Odd Harmonics < <20 4 20<50 7 50<100 10 100<1000 12 >1000 15 Even harmonics are limited to 25% of the odd harmonic limits above Current distortions that result offset, e.g., half wave converters are not allowed. * All power generation equipment is limited to these values of current distortion regardless of actual Isc / I ...

Page 4

Zero Sequence Filter(ZSF) General 〉 1. General Increasing use of computer and electric home appliance, the neutral current zero sequence harmonic in line make variety types of disturbances in system. ZSF(Zero Sequence Filter) is easy to install with electric accessories and it can reduce this large neutral current up to 90% depending on the installed position. 2. The problems of Zero Sequence harmonics •Trip the circuit breaker due to overcurrent • Malfuction of electric protector • Communication disturbance 3. Application •Applicable load : C omputer, OA appliance, Electronic fluorescent lamp, Single Phase SCR heater and UPS etc •Applicable system : Single phase nonlinear loads on Three phase four wire systerm •Applicable place : Office/Commercial Building, School, Apartment, Department, Factory, Medical center etc. Features 〉 •Neutral impedence adjuster upon request •Easy to Install •Increasing power quality Effects ...

Page 5

Samwha Creative TEchnology Provider 4-3. Hybrid Harmonic Filter(HHF) General 〉 1. General The Hybrid Harmonic Filter(HHF) enable most three phase non-linear load to comply with both the voltage and current distortion limits of IEEE Std.519-1992 and other international limits such as AS-2279, EN61000-3-4, and BS G5/4. Comparing with the classical broad band harmonic filter, the HHF have only 30% of capacitance with better filtering. Less capacitance can minimize leading current at light loading condition. 2.Problems of Harmonic •Resonance at Power •Trip the Relay or cut fuse 3. Application •Applicable loads : Inverter, UPS, Elevator, AC/DC motor drive, Diode/SCR Rectifier, Induction heater, DC power supply, HVAC system, Fan and Pumps etc. •Applicable place : Office/Commercial building, School, Shopping Mall, Department store, Apartment, Hospital, Factory etc •Applicable system : Low Voltage 3P nonlinear loads Features 〉 •Patent No.0383791 as Hybrid Harmonic Filter •Qualified as Excellent Product by the ministray of commerce, industry and energy •Compact and easy-to-install. •Standardized up to 1000HP (based on load capacity) ...

Page 6

L-C Complex Harmonic Filter(LCF) General 〉 1. General The motor using inverter is causing riffle wave form on voltage, and it causes many problems on the system like breaking down dielectric. LCF can convert PWM wave form to sine wave form making more safe operation in the system. 2. Problems of Harmonic •Destroying dielectric in Motor by spike •Damage on Voltage raising transformer •Malfuction and reduced life spam of Inverter by inversed voltage. •Instantaneous Over voltage phenomenon by distorted voltage wave form •Malfuntion of precision apparatus 3. Application •Applicable load : Motor and machines using inverter(Between inverter and motor) •Applicable system: 220V, 380V, 440V, 1000HP •Applicable place : Plants, Steel Mills, power plant, sewage disposal plants, Garbage dumps etc Features 〉 •Make smooth voltage and current wave form •Reduce voltage reflection and surge impedance Effects 〉 •Prevent dielectric destruction •Increase productivity and quality •Increase system communication quality and life span Standard specification ...

Page 7

Samwha Creative TEchnology Provider 4-5. Active Power Harmonic Filter(APF) General 〉 1. General The proliferation of nonlinear loads such as static power converters and arc furnaces results in variety of undesirable phenomena in the operation of power systems. The most important among these are harmonic contamination, increased reactive power demand and power system voltage fluctuations. Harmonic currents increase power systems losses, excessive heating in rotating machinery, can create significant interference with the power line communication. The harmonic is a growing problem for both electricity suppliers and consumers. 2. Problems of Harmonic •Malfunction of precision control •High current in neutral conductors •Damage to sensitive equipment •Frequent tripping of circuit breakers 3. Application •Applicable load : W elding Machine, Electrolyzer in Chemical Factory, Electrolytic machine of ceramic plasitc, Arc furnace, Crain etc •Applicable system : 380V, 440V, 50-300A •Applicable place : Steel Mills, Chemical Plants, Metal mills, Harbors etc Features ...

Page 8

Intelligent Var Compensator(IVC) General 〉 1. General Intelligent Var Compensator(IVC) is the product designed to improve power quality in the systems with welding, crane and many unspecified loads which is generating reactive power. 2. Application •Applicable loads : Welding machines, Arc furnace, unspecified loads generating reactive power, •Applicable system: 380V, 440V, 30~1800kvar •Applicable place : Steel mills, Chemical plants, Metal mills, Harbors etc. Features 〉 •Patent No.0459000 •3Phase 4Wire reactive power compensation system with linear response characteristics. •Prevent the voltage drop and flicker with 5-20ms response speed. •Control the reactive power using power switching sockets without transient •Protect senstive electric machines and save energy •Exact and fast power factor improvement Effects 〉 •Power factor on the secondary side of transformer is improved at 98% •Average current is decreased to 30% •Prevent voltage flicker phenomenon through resolving reactive power in real-time <Before installing IVC> <After installing IVC> Standard specification 〉 Capacity ...

Page 9

Samwha Creative TEchnology Provider 4-7 Low Frequnecy Induction Furnace Capacitor Application 〉 This product was developed in 1977 with the purpose of rationalizing power supply by improving heat efficiency and power factor of Low Frequency Induction Furnace. This product consists of polypropylene film, aluminum thin film or metalized film which has excellent voltage resistance. It contains specially produced composite oil, resulting in high reliability. Product Scope 〉 • Installation Place : Indoor • Ambient Temperature for use : -20℃ ~ +40℃ [below 35℃ average for 24 hours] Technical Data 〉 Tolerance Withstand Voltage Insulation Level Max Overvoltage Max overcurrent Capacitor Loss [Under stabilized condition] Diagram 〉 Figure 1 Samwha +15% [at 20℃] 10 seconds of 2.0 times of rated voltage between mutual terminals 2U ...

Page 10

... SMFL-66100KS 343 153 380 455 205 200 SMFL-86100KS 343 153 470 545 205 200 SMFL-66150KS 630 135 500 575 205 100 SMFL-86150KS 343 153 640 715 295 200 SMFL-66200KS 343 153 660 735 255 200 SMFL-76200KS 343 153 580 655 255 ...

Page 11

Samwha Creative TEchnology Provider 4-8 Water Cooling Capacitor Application 〉 This product is specially designed to accommodate high capacity to be easily used for matching circuit of high frequency induction furnace device. For dielectric, polypropylene film and capacitor paper was used together and aluminium foil electrode of non induction method ...

Page 12

Water Cooling Capacitor Diagram 〉 Figure 1 Figure 3 Ratings and Dimensions 〉 Frequency Rated Votage Rated Capacity Total [Hz] [VAC] [kvar] [㎌] 960 800 450 117 960 1000 480 80 13 1000 1250 750 76 1200 1250 1200 102 2000 1250 300 ...

Page 13

Samwha Creative TEchnology Provider 4-9 Surge Absorbing Capacitor Application 〉 This product was developed by our company in 1976 to absorb and reduce surge which may be generated when the breaker is open or closed and lighting surge by connecting transmission line and, closed and lightning surge which may be delivered by connecting transmission line and ground. Its dielectric is polypropylene film which has excellent withstand voltage and good quality capacitor paper and it also contains specially produced composite oil. The Capacitor with series resistance was developed to improve electric feature. Product Scope 〉 • Installation Place : Indoor / Outdoor • Ambient Temperature : -20℃ ~ +40℃ [below average 35℃ per day, below 25℃ average per year] Technical Data 〉 Tolerance -5% ~ +15% [at 20℃], less than 108% of unbalanced ratio between phases Below 110% of rated voltage : within 8 hours per day Below 115% of rated voltage : within 30 minutes per day Max overvoltage ...

Page 14

Surge Absorbing Capacitor Figure 1 Ratings and Dimensions 〉 Rated Voltage Rated Capacity [VAC] √ 3300/ 3 0.05 ㎌ THF-T30015T [CR] √ 3300/ 3 0.1 ㎌ THF-T3003T [CR] √ 3300/ 3 0.5 ㎌ THF-T305T √ 3300/ 3 0.8 ㎌ THF-T3024T √ 6600/ 3 0.05 ㎌ THF-T60015T [CR] √ 6600/ 3 0.1 ㎌ THF-T6003T [CR] √ 22900/ 3 0.1 ㎌ THF-T23001S ...

Page 15

Samwha Creative TEchnology Provider 4-9 Surge Absorbing Capacitor Operation principle 〉 To explain the effect of surge absorbing capacitor, the rotator is expressed as intensive equivalent resistance the figure A. In parallel with this, on the circuit to which the protecting Capcitor is connected EOH[t] travelling wave invaded from line of surge impedance Z. Then, when terminal voltage of R and C is Vc, the current point i dVc ── + ─ rearrange the expression ── = ...

Page 16

Grounding Capacitor Application 〉 This porduct was developed by our company in 1975 to improve capacity between distribution line and earth by connecting the 2nd winding distribution line of insulation transformer and earth. It uses polypropylene film which has excellent insulation ability and good quality capacitor paper as dielectric and contains specially produced composite oil to improve electric feature. Product Scope 〉 •Installation Place : Indoor / Outdoor •Ambient Temperature : -20℃ ~ +40℃[below 35℃ average per day, below 25℃ average per year] Technical Data 〉 Tolerance -5% ~ +15% [at 20℃], less than 108% of unbalanced ratio between phases Below 110% of rated voltage : within 12 hours per day Below 115% of rated voltage : within 30 minutes per day Max overvoltage Below 120% of rated voltage : within 5 minutes Below 130% of rated voltage : within 1 minute Below 182% of rated voltage : within 2 seconds Max overcurrent Transient current 130% of rated current allowed Between case and all of terminals Line voltage Withstand Voltage 3300V 6600V Capacitor Loss Less than 0.35% [at rated voltage, 20℃] Painting Color Munsell no. 5Y 7/1 Reference Standard JEM1362 [1999] Diagram 〉 ...

Page 17

Samwha Creative TEchnology Provider 4-10 Grounding Capacitor Ratings and Dimensions 〉 Line Voltage [V] Rated Capacity [kvar] 3300 6600 * A pproximate Dimensions are give above. Please contact factory for exact deimensions of a particular capacitor Operation Principle 〉 phase circuit, for 1 line grounding current is calculated from the following formula. √ 3jωCEa = j 3E×2π Grounding Current [ Phase Voltage [V] I [Ground fault current Ig in figure A - charged current after zero phase current transformer [ZCT]] C1 passes the zero phase current transformer. Therefore, ground fault current ...

Page 18

Pulse Power Capacitor Application 〉 normally used in the area of power supply device for tests,for example IVG, ICG, Mark Generator, Power Supply for L-C resonance circuit and small scale power supply for fusion study and Power supply pulse power[state of art medical instruments, rock destruction and pulse laser] and recently, households which use this capacitor have been rapidly increased. Since high energy density capacitor for pulse power is the key part of aircrafts [fighter, artificial satellite and passenger airplane], electronic / electric heat chemical gun, high efficiency laser and high efficiency munitions such as radar, the supply of this product was difficult since the industrialized countries regulated the outflow of technology. But, recently our company mass porduced the capacitor resulting in smooth supply of the product. In 1997, 11kVDC 150㎌ 9kJ rated capacitor for energy storage was developed with our own technology and delivered them for power supply of simple composite test facility and its performance has been recognized. Several capacitors were also installed at heavy electro mechanics manufacturers in Korea and are used for test facilities. Figure 1 PulsePower Low Capacitor 〉 This product uses polypropylene film which has excellent withstand voltage and good quality capacitor paper as dielectric and contains refined impregnation oil, resulting in high reliability. To minimize inner ...

Page 19

Samwha Creative TEchnology Provider 4-11 Pulse Power Capacitor Ratings and Dimensions 〉 Rated Volage Joule Capacity Type [kVDC] [kJ] [㎌] 11 150 9.08 TFT-T11150S 810 995 160 315 370 424 228 0.01 0.01 TFT-T40001S 190 375 115 315 430 496 300 ...