TL100048 TDK Corporation, TL100048 Datasheet - Page 25

PWR SUP FNT END 48V 1000W 20A

TL100048

Manufacturer Part Number
TL100048
Description
PWR SUP FNT END 48V 1000W 20A
Manufacturer
TDK Corporation
Series
TLr
Datasheets

Specifications of TL100048

Power Supply Type
Switching (Closed Frame)
Voltage - Output
48V
Number Of Outputs
1
Power (watts)
1000W
Applications
Commercial
Voltage - Input
90 ~ 264VAC
Mounting Type
Chassis Mount
1st Output
48 VDC @ 20A
Size / Dimension
11.12" L x 3.41" W x 3.45" H (282.4mm x 86.6mm x 87.6mm)
Power (watts) - Rated
1000W
Operating Temperature
-40°C ~ 65°C
Efficiency
92%
Approvals
CE, CSA, EN, UL
Line Regulation
±1%
Load Regulation
±1%
Power Supply Output Type
Fixed
No. Of Outputs
1
Output Voltage
48V
Output Current
20A
Power Rating
1000W
Input Voltage
90V AC To 264V AC
Length
282.448mm
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
285-1646
7 Troubleshooting
7.1 Problems and Solutions
The modular, plug-n-play nature of this plant makes diagnostics and repair very easy. Make sure
that all power modules are properly seated and latched into their respective slots. Make sure that
all power and signal connectors are properly mated. Table 13 lists problems and potential solutions.
7.2 Short circuit & Current Limit
ILimit can be adjusted up to +105% of the rated current of the power module. The system voltage
will remain constant up to ILimit at which point the system voltage will drop quickly toward 0 VDC,
as in Figure 15. Once a 24V or 48V power module drops below 12 VDC for more than 5 seconds,
the system will shut down. For a 12V system, once the power module drops below 4V for more than
60 seconds, the system will shut down. The system will automatically restart after 60 seconds, and
will continue until the short circuit is cleared.
3055 Del Sol Blvd • San Diego, CA 92154 • 1-800-LAMBDA-4
Problems and Solutions
Problem
DC OK LED extinguished or
Module DC fail via alarm cable
AC OK LED Extinguished or
Module AC fail via alarm cable
Thermal Limit Failure
Figure 15 - Short Circuit & Current Limit
Table 13 - Problems and Solutions
Solution
Replace bad power module unit - unlatch, remove and replace with spare.
System short circuit - inspect and replace load and wiring.
Reset commercial circuit breaker to the dedicated AC circuit that feeds system.
Seek alternative power source until power is restored.
Power module has shut down because it has exceeded the maximum rated
temperature. The power modules will automatically restart.
TLR5-S S ERIES POWER SYSTEM
Revision 1 : January 2006
Page. 25

Related parts for TL100048