TL100048 TDK Corporation, TL100048 Datasheet - Page 9

PWR SUP FNT END 48V 1000W 20A

TL100048

Manufacturer Part Number
TL100048
Description
PWR SUP FNT END 48V 1000W 20A
Manufacturer
TDK Corporation
Series
TLr
Datasheets

Specifications of TL100048

Power Supply Type
Switching (Closed Frame)
Voltage - Output
48V
Number Of Outputs
1
Power (watts)
1000W
Applications
Commercial
Voltage - Input
90 ~ 264VAC
Mounting Type
Chassis Mount
1st Output
48 VDC @ 20A
Size / Dimension
11.12" L x 3.41" W x 3.45" H (282.4mm x 86.6mm x 87.6mm)
Power (watts) - Rated
1000W
Operating Temperature
-40°C ~ 65°C
Efficiency
92%
Approvals
CE, CSA, EN, UL
Line Regulation
±1%
Load Regulation
±1%
Power Supply Output Type
Fixed
No. Of Outputs
1
Output Voltage
48V
Output Current
20A
Power Rating
1000W
Input Voltage
90V AC To 264V AC
Length
282.448mm
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
3rd Output
-
2nd Output
-
4th Output
-
Lead Free Status / RoHS Status
Lead free / RoHS Compliant, Lead free / RoHS Compliant
Other names
285-1646
TLR5-S S ERIES POWER SYSTEM
Figure 3 - Individual Feed AC Wiring Architecture
An individual feed architecture powers one power module slot per AC feed. Connect the feed,
sized according to section 2.2.3, into IEC320 plugs as seen in Figure 9. There are two different
types of individual AC feeds. The first type of AC connection is made with IEC320 connectors
that are rated for a maximum of 15 amps. Do not connect this type of individual AC system to
an AC breaker larger than 15 amps. The second type of AC connection is made with IEC320
connectors that are rated for a maximum of 20 amps. Do not connect this type of individual AC
system to an AC breaker larger than 20 amps. See section 2.2.2 for help determining your AC
architecture type.
2.3.3 Sizing AC feeds
To size your AC feeds properly, use Table 5, Table 6, and Table 7. Failure to size the AC breaker
and wiring properly can result in nuisance breaker trips or even damage to the equipment.
Follow the example below for determining AC breaker and wire sizing.
Use section 2.2.2 to determine the AC input type, for example a dual feed. Next determine the
number and model number of the power modules. Use Table 4 to determine the required AC
input voltage.
Page. 9
3055 Del Sol Blvd • San Diego, CA 92154 • 1-800-LAMBDA-4
Revision 1 : January 2006

Related parts for TL100048