WS02-CXPC1-EV2.0 Omron, WS02-CXPC1-EV2.0 Datasheet - Page 19

Development Software

WS02-CXPC1-EV2.0

Manufacturer Part Number
WS02-CXPC1-EV2.0
Description
Development Software
Manufacturer
Omron
Datasheet

Specifications of WS02-CXPC1-EV2.0

Rohs Compliant
NA
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
WS02CXPC1EV20
Communications
J NT LINK FOR PROGRAMMABLE TERMINALS
1:1 NT Link
High-speed communications can be achieved by providing a
direct access through the use of the 1:1 NT Link between the
SRM1 and Omron’s NT-Series Programmable Terminals. The
RS-232C port can be used for NT Link. The peripheral port can
be converted to RS-232C port using the CPM1-CIF01 serial
communication adapter.
J HOST LINK COMMUNICATIONS
Host Link is a command/response communications system in
which commands are transmitted from the host computer and
corresponding responses are returned from the destination
SRM1. Host Link commands can be used to read/write data in
SRM1 data areas and read/write settings. Either the peripheral
port or RS-232C port can be used.
1:1 Host Link Connection
The SRM1 can be connected to an IBM PC/AT or compatible
computer or a Programmable Terminal, as shown in the following
diagram.
SRM1
IBM PC/AT or com-
patible computer
Programmable Terminal
C200H-CN320-EU
cable (3 m)
SRM1
SRM1
Programmable
Terminal
1:N NT Link
Connect the SRM1 to several NT–Series Programmable
Terminals via the peripheral port using the CPM1-CIF11 serial
communication adapter, as shown in the illustration at below.
OMRON PTs that support the 1:N NT Link must be used.
Programmable
Terminals
SRM1
Host Link
computer
RS-422
CPM1-CIF11
Peripheral to
RS-422/RS-485 adapter
Command
Response
SRM1
SRM1
SRM1