WS02-CXPC1-EV2.0 Omron, WS02-CXPC1-EV2.0 Datasheet - Page 7

Development Software

WS02-CXPC1-EV2.0

Manufacturer Part Number
WS02-CXPC1-EV2.0
Description
Development Software
Manufacturer
Omron
Datasheet

Specifications of WS02-CXPC1-EV2.0

Rohs Compliant
NA
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Other names
WS02CXPC1EV20
J COMPOBUS/S COMMUNICATIONS SPECIFICATIONS
Note: 1. A terminator must be connected to the point in the system farthest from the Master.
J TERMINATORS
Ratings/Characteristics
Materials
SRM1
Communications method
Coding method
Connection method
Communications
baud rate
(See Note 2.)
Communications
cycle time
Maximum number of connectible terminals
Communications
distance
Cable
Number of points per CPU
Error control checks
Rated current
Contact resistance
Insulation resistance
Withstand voltage
Cable pulling strength
Operating temperature
Housing
Cover
Contact
2. The communications baud rate is switched using DM settings (default setting is 750 kbps).
High-speed mode
Long-distance mode
High-speed mode
Long-distance mode
High-speed mode
Long-distance mode
Vinyl-clad VCTF
JIS C3306
Flat cable
CompoBus/S protocol
Manchester coding method
Multi-drop method and T-branch method (See Note 1.)
750 kbps
93.75 kbps
0.8 ms, when maximum number of connectible terminals is 32
0.5 ms, when maximum number of connectible terminals is 16
6.0 ms, when maximum number of connectible terminals is 32
4.0 ms, when maximum number of connectible terminals is 16
32: 16 IN and 16 OUT
16: 8 IN and 8 OUT
Belden #9409 or VCTF cable:
Main line length: 100 m max.
Branch-line length: 3 m max.
Total length of branches: 50 m max.
Flat cable (SCA1-4F10):
Main line length: 30 m max.
Branch-line length: 3 m max.
Total length of branches: 30 m max.
(When flat cable is used to connect fewer than 16 Slaves, the main line can be up to
100 m long and total branch line length can be up to 50 m.)
Belden #9409 or VCTF cable:
Main line length: 500 m max.
Branch-line length: 6 m max.
Total length of branches: 120 m max.
Two 0.75 mm
Four 0.75 mm
256 (128 IN and 128 OUT), when maximum number of connectible terminals is 32.
128 (64 IN and 64 OUT), when maximum number of connectible terminals is 16.
Manchester code check, frame length check, parity check, two-transfer comparison
4 A
20 mΩ max.
1,000 MΩ min. at 500 VDC
1,000 VAC for 1 min, leakage current: 1 mA max.
50 N (5.1 kgf) min.
–20 °C to 70°C (–4°F to 158°F)
PA66 resin (UL94V-2)
Branching and extension: Gray
Terminator: Black
Phosphor bronze and nickel base, tin plated
2
2
conductors (2 signal wires)
conductors (2 signal wires and 2 power supply wires)
SRM1
7

Related parts for WS02-CXPC1-EV2.0