BCCM6033SQ Cooper/Bussmann, BCCM6033SQ Datasheet - Page 183

no-image

BCCM6033SQ

Manufacturer Part Number
BCCM6033SQ
Description
FUSEBLOCK CLASS CC 13/32X1-1/2"
Manufacturer
Cooper/Bussmann
Series
BCCMr
Type
Blockr
Datasheet

Specifications of BCCM6033SQ

Fuse Size
Class CC
Number Of Circuits
3
Mounting Type
Chassis Mount
Termination Style
Screw Terminal
Current Rating
20A
Product
Block
Fuse Size / Group
Class CC
Voltage Rating
600 Volts
Mounting Style
Screw
Body Material
Thermoplastic
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Voltage
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Dimensional Data
15800-R-200
15800
Fused Disconnect Switch
Ampere Ratings: 3 to 70A.
Voltage Rating: 60Vdc
Agency Information:
UL Recognized, Guide QPQY2, File E97649
UL Withstand Rating: 100,000A,
Catalog Numbers
15800-R-200
15800-F-200
• For use with the following fuses only:
• Alarm output with wire wrap terminal or connection to .063”
• Thermoplastic housing material U.L. rated
• Spare alarm and power fuse compartment.
• Mounting hardware included.
• Spare fuseholders:
Main: Telpower
Alarm: Bussmann GMT-A only (page 183).
Recommend GMT-X Cover (page 183).
thick common alarm bus.
94V-0, 150°C.
for TPS fuses (TPSFH-AS);
for GMT fuses (TPSFH-T), see page 196.
Telpower
Fused Disconnect Switch
For complete specification data, call Bussmann Information Fax ~ 636.527.1450
®
®
TPS 3 to 70 Amp
DC Power Protection Systems
Rear Access Panel Mounting
Front Access Panel Mounting
Data Sheet: 5002
TPS
Ampere Ratings: 1 to 70A.
Voltage Rating: 170Vdc
Agency Information:
UL Recognized, Guide JFHR2, File E56412
Catalog Numbers
TPS-1
TPS-1L
TPS-2
TPS-2L
TPS-3
TPS-3L
TPS-5
TPS-5L
TPS-6
• TELPOWER fuse line is the first to be specifically designed
• The UL Recognized ratings of 170Vdc and 100,000A
• A unique BLUE label is used on all TELPOWER fuses to
• Circuit board applications available.
• Silver-plated brass ferrules.
• Glass melamine tube.
• For use with Bussmann Fused Disconnect Switch 15800.
• Spare Fuseholder: TPSFH-AS, see page 198.
• Printed circuit board variations available.
Dimensional Data
to meet the unique needs of DC Power Distribution
Systems.
designate their DC capability.
interrupting rating along with the fuse’s current limiting
capability make this fuse ideal for cable protection on exist
ing DC Distribution Systems.
TPS-6L
TPS-10
TPS-10L
TPS-15
TPS-15L
TPS-20
TPS-20L
TPS-25
TPS-25L
TPS-30
TPS-30L
TPS-35
TPS-35L
TPS-40
TPS-40L
TPS-40V
TPS-50
TPS-50L
Bussmann
Data Sheet: 5009
TPS-50V
TPS-60
TPS-60L
TPS-70
TPS-70L
TPS-70LB
179
®