BCCM6033SQ Cooper/Bussmann, BCCM6033SQ Datasheet - Page 184

no-image

BCCM6033SQ

Manufacturer Part Number
BCCM6033SQ
Description
FUSEBLOCK CLASS CC 13/32X1-1/2"
Manufacturer
Cooper/Bussmann
Series
BCCMr
Type
Blockr
Datasheet

Specifications of BCCM6033SQ

Fuse Size
Class CC
Number Of Circuits
3
Mounting Type
Chassis Mount
Termination Style
Screw Terminal
Current Rating
20A
Product
Block
Fuse Size / Group
Class CC
Voltage Rating
600 Volts
Mounting Style
Screw
Body Material
Thermoplastic
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Voltage
-
Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Data Sheet: 5021
180
TP158HC
Fused Disconnect Switch
For use with Telpower® Fuses Type TPL-B.
Ampere Ratings: 70-250A
Voltage Rating: 80Vdc
UL Withstand Rating: 100,000A
Agency Information:
UL Recognized (investigated to UL 1801) as a
disconnect switch for the interruption of load current
by means of withdrawing the fuse pullout.
Guide QPQY2, File E97649.
Catalog Numbers:
TP158HC: Rear Access, Panel Mounting, English
TP158HC: Rear Access, Panel Mounting, Metric
General Information:
• High amp version of Bussmann 15800 series
• Similar profile, mounting method, and backplane
• Innovative new fuse pullout design eliminates
• For use with the following fuses only:
• Alarm output with wire wrap terminal or connection to
• Hardware included:
Fused Disconnect Switch.
configuration as 15800 Series. The TP158HC
can be installed into existing 15800 Series panels
using the space of two 15800 disconnects.
need for tools to replace the Telpower® type
TPL-B fuse.
.063” thick common alarm bus.
Load: washer, split lockwasher, and 5/16 _ 18 nut.
Fused Disconnect Switch
Main: Telpower® TPL-B 70-250 Amperes.
Alarm: Bussmann GMT-A only.
Telpower
®
DC Power Protection Systems
For complete specification data, call Bussmann Information Fax ~ 636.527.1450
• Thermoplastic housing material UL rated 94V-0, 150°C.
• Spare fuseholders:
• Application Note: The line connection uses a 1/4-20 bolt
• Application Note: The alarm circuit is not intended for
precharging of capacitive circuits. Alarm circuit current
1A maximum.
for TPL-B fuses (TPSFH-LB), see page 14;
for GMT fuses (TPSFH-T), see page 14.
(metric – M6X1) that threads into the line terminal. The line
terminal is designed with a float of ±.02 in. (± .50mm) to
allow for variation in the distance between the TP158HC
mounting flange and the line bus bar (see dimensional
data). Equipment should be designed to eliminate any rel-
ative movement between the TP158HC mounting flange
and the line bus bar.
Easy Fuse Replacement
TP158HC
Bussmann
®