DMPR3-E-3/4/5-36KW UA (UNITED AUTOMATION), DMPR3-E-3/4/5-36KW Datasheet - Page 2

no-image

DMPR3-E-3/4/5-36KW

Manufacturer Part Number
DMPR3-E-3/4/5-36KW
Description
DUAL MODE POWER REG. 230V 36KW
Manufacturer
UA (UNITED AUTOMATION)
Datasheet

Specifications of DMPR3-E-3/4/5-36KW

Approval Bodies
CE
External Depth
232mm
External Length / Height
124mm
External Width
322mm
Fixing Centres
6mm
Fixing Centres Lxw
322x200
Input Voltage Max
400V
Mounting Type
Flange
Operating
RoHS Compliant
OPTIONAL EXTRAS
A403011
5K 1W potentiometer with 0.5m long lead for manual control option
INSTALLATION
COOLING REQUIREMENTS
Heatsink temperature rating for standard stack assembly is calculated when naturally cooled. If mounted in enclosure or cabinet, adequate
ventilation and/or forced air-cooling should be fitted. Thermal trips are fitted on 75A to 100A rated controllers. This is in order to switch off the
thyristors in an over temperature situation, which is indicated by an LED. The trip resets when the temperature falls below 90° C.
LOAD CONSIDERATIONS
It is always advisable to indicate the type of load when ordering. For industrial reliability, based on long experience, the SAC range has
considerable current overload capacity on the power devices used. The rated currents are maximum continuous RMS values for use within the
temperature guidelines as shown in the table below.
Unusual heating loads such as Molybdenum, Platinum or Tungsten have a typical 10 to 1, hot to cold, resistance ratio and therefore, when cold,
draw larger currents than normal. Transformers and other inductive loads have surge starting currents and require the correct type of phase
angle firing circuit. These and similar types of surge loads should be indicated, so that appropriate slow start or larger rated units can be correctly
supplied for the specific needs.
Fusing
It is recommended that fast acting semiconductor type fuses (as supplied) be used for protection. See SRA Data sheet X10255 for further
information. Other external supplies should be fused accordingly.
CE Marking
This family carries a “CE” marking, In burst fire mode the controllers do not normally require a remote filter. For more information contact our
sales desk. A Declaration of Conformity available on request.
RECOMMENDATIONS
These supporting documents, which may be appropriate for your application, are available on request,
CODE
X10213
X10255
X10322
X10617
NOTE:- It is recommended that installation and maintenance of this equipment should be carried out by suitably qualified/trained personnel with
reference to the current edition of the I.E.E. wiring regulations (BS7671 The regulations contain important requirements regarding the safety of
electrical equipment. For International Standards refer to I.E.C/ Directive IEC 950.
© These products are protected by unregistered design with United Automation Limited, Southport, UK
Product Reference
ORDERING
DMR3-36kW
DMR3-54kW
UNITED AUTOMATION LIMITED
IDENTITY
ITA
SRA
APC
Description Ratings (RMS)
230V, 18kW, 50A
230V, 30kW, 80A
1Southport Business Park
Kew
Southport, PR8 4HQ
ENGLAND
Page No. 2 of 2
Maximum Heatsink
Ambient
30°C
40°C
50°C
60°C
DESCRIPTION
Interaction, uses for phase angle and for burst fire control.
Safety requirements:- Addressing the Low Voltage Directive(LVD) including:- Thermal
data/cooling, ‘Live’ parts warning, Earth requirements and fusing recommendations.
AC Power Control – Three phase application circuits
Wiring connection details are attached to the inside of the lid.
Issue 1
Tel: 0044 (0) 1704 – 516500 Main
Enquiry@united-automation.com
www.united-automation.com
Fax: 0044 (0) 1704 – 516501
Date 20/01/09
CONNECTIONS
Maximum RMS Line Current
(3 Phase Supply)
100A
85A
75A
65A