FC4A-K2C1 IDEC, FC4A-K2C1 Datasheet - Page 38

no-image

FC4A-K2C1

Manufacturer Part Number
FC4A-K2C1
Description
Analog Output Module
Manufacturer
IDEC
Datasheet

Specifications of FC4A-K2C1

Supply Voltage
24VDC
No. Of Analog Outputs
2
Output Voltage Dc Max
10V
External Height
90mm
Supply Voltage Min
20.4V
Operating Voltage Max
10V
Operating Voltage Min
-10V
External Width
23.25mm
External Depth
70mm
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
For Use With
MicroSmart CPU Module
4: A
4-16
Ladder Refresh Type
The operating status of each analog output channel is stored to a data register determined by the data register number
selected in the Configure Parameters dialog box of the ANST macro.
Bit 4 to Bit 15
Status Code
Operating Status Bit
NALOG
Bit 0
Bit 1
Bit 2
Bit 3
0
1
2
3
4
I/O C
Normal operation
(reserved)
Initializing
Invalid parameter or analog output channel not available on the installed analog module
Hardware failure (external power supply failure)
ONTROL
0
1
0
1
0
1
0
1
0
Operating status bit
Parameter bit
External power supply bit
Output data error bit
Reserved
FC4A M
ICRO
Analog Output Operating Status (END refresh type)
S
MART
Analog Output Operating Status (Ladder refresh type)
A
NALOG
Normal operation
Initializing, changing configuration, hardware initialization error
Parameter configuration normal
Parameter configuration error
External power supply normal
External power supply error
Output data normal
Output data range error
Normal operation
I/O M
ODULE
U
SER
S
M
ANUAL