PC Errors
5-4
5-4-1 Initialization Errors
5-4-2 Non-fatal Operating Errors
CPU wait
CPU wait
CPU wait
CPU wait
System FAL
JMP error
DM address error
SFC cont error
I/O verify error
CPU Bus Unit error
SYSMAC BUS/2 error
SYSMAC BUS error
Programming Console
Programming Console
error message
error message
PC Errors
Note The I/O table verification error can be set as an initialization error in the PC
Start input on CPU Rack’s
Power Supply Unit is OFF.
Power to Slave is off or
terminator is missing.
Initializing CPU Bus Unit or
SYSMAC BUS/2 terminator
missing.
A Unit has been changed
making the I/O table
incorrect.
(PC Setup)
FAL(006) has been executed in
program. Check the FAL number
to determine conditions that
would cause execution
(programmed by user).
No JMP(004) in the program.
Indirectly addressed DM address
data is not BCD.
An error has occurred during
SFC execution.
Unit has been removed making
I/O table incorrect.
A parity error has occurred in the
transfer of data between the
CPU Unit and a CPU Bus Unit or
in the CPU Bus Link.
An error has occurred between a
Master and Slave Rack.
An error has occurred between a
Master and Slave Rack.
Probable cause
The following errors occur before program execution has been started. The
POWER indicator will be lit and the RUN indicator will not be lit for any of these.
The RUN output will be OFF for each of these errors. The alarm indicator
(ALARM) will be ON for the I/O table verification error.
Setup.
The following errors occur after program execution has been started. PC opera-
tion and program execution will continue after one or more of these errors have
occurred. For each of these errors, the POWER, RUN, and ALARM indicators
will be lit and the ERROR indicator will not be lit. The RUN output will be ON.
Probable cause
A30600
A30602
A30603
A30601
A40209
Flag(s)
A40215 4101 to 42FF
A40213 00F9
A40212 00F8
A40211 00F4
A40209 00E7
A40207 0200 to 0215
A40206 00B0 to 00B3
A40205 00A0 to 00A7
Flag(s)
None
None
None
00E7
Error code
(A400)
correspond to
FAL numbers
001 to 511.
or 0231
(Masters
#0 to #3.)
(Masters
#0 to #7.)
Error code
(A400)
1
2
3
Short start input terminals on
CPU Unit’s Power Supply Unit.
Check power supply to Slaves
and terminator setting.
Wait for CPU Bus Unit
Initialization to be completed.
Check power supply to Slaves
and terminator setting.
Check the I/O table from the
CVSS/SSS and either connect
Dummy I/O Units or correct the
I/O table.
Correct according to cause
indicated by FAL number
(set by user).
Check and correct the
program.
Check and correct the
program. (Refer to the next
table for information on
non-fatal SFC errors.)
Check the I/O table from the
CVSS/SSS and either
connect Dummy I/O Units or
correct the I/O table.
Check the errant Unit.
Verify that the Slave Rack is
operating properly, and
check the transmission line.
Verify that the Slave Rack is
operating properly, and
check the transmission line.
Possible remedy
Possible remedy
Section 5-4
121