T1610000 Red Lion Controls, T1610000 Datasheet - Page 21

Process/Temperature Controller

T1610000

Manufacturer Part Number
T1610000
Description
Process/Temperature Controller
Manufacturer
Red Lion Controls
Type
Temperaturer
Datasheets

Specifications of T1610000

Operating Temperature Max
50°C
Operating Temperature Min
0°C
Output Voltage Max
250VAC
Controller Input
Thermocouple Or RTD
Supply Voltage Max
250VAC
Mounting Type
Panel Mount
Brand/series
T16 Series
Contact Form
SPST
Dimensions
49.5mmW×49.5mmH×115.3mmD
Enclosure Rating
IP65
Input Type
RTD/Thermocouple
Ip Rating
IP65
Memory
EEPROM
Output Type
Relay
Power, Rating
8 VA
Primary Type
Controller
Special Features
EEPROM
Standards
cURus, CE
Termination
Screw
Voltage, Supply
85 to 250 VAC
Thermocouple Type
J, K, T, E, R, S, B, N, C And Linear MV
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
ON/OFF CONTROL
to 0.0%. In this control mode, the process will constantly oscillate around the
setpoint value. The On/Off Control Hysteresis (balanced around the setpoint)
can be used to eliminate output chatter. Output O1 Control Action can be set to
reverse for heating (output on when below the setpoint) or direct for cooling
(output on when above the setpoint) applications.
Note: CHYS in the On/Off Control Figures refers to the On/Off Control Hysteresis
Alarm 2 Action is set to cooling (O2). The Proportional Band is set to 0.0 and
the Relative Gain in Cooling to 0.0. The Deadband in Cooling sets the amount
of operational deadband or overlap between the outputs. The setpoint and the
On/Off Control Hysteresis applies to both O1 and O2 outputs. The hysteresis is
balanced in relationship to the setpoint and deadband value.
PID CONTROL
control output power value by use of a modified Proportional Band, Integral
Time, and Derivative Time control algorithm. The system is controlled with the
new output power value to keep the process at the setpoint. The Control Action
for PID Control can be set to reverse for heating (output on when below the
setpoint) or direct for cooling (output on when above the setpoint) applications.
For heat and cool systems, the heat (O1) and cool (O2) outputs are both used.
The PID parameters can be established by using Auto-Tune, or they can be
Manually tuned to the process.
C
The controller operates in On/Off Control when the Proportional Band is set
(
For heat and cool systems, O1 Control Action is set to reverse (heat) and the
In PID Control, the controller processes the input and then calculates a
CHYS
ONTROL
) in parameter Module 2.
REVERSE OR DIRECT ACTING FIGURES
ON/OFF CONTROL -
M
ODE
E
XPLANATIONS
21
ON/OFF CONTROL - HEAT/COOL OUTPUT FIGURES
TYPICAL PID RESPONSE CURVE