Humidity And Temperature Control

01230.9-01

Manufacturer Part Number
01230.9-01
Description
Humidity And Temperature Control
Manufacturer
STEGO
Datasheet

Specifications of 01230.9-01

Mounting Type
DIN Rail
Operating Voltage Max
120V
Operating Temperature Max
60°C
Output Type
Temperature
Supply Voltage
120VAC
Temperature Accuracy ±
1K
Humidity Range
50 To 90% RH
Operating Temperature Min
0°C
Rohs Compliant
Yes
Lead Free Status / RoHS Status
Lead free / RoHS Compliant
Specifications are subject to change without notice. Suitability of this product for its intended use and any associated risks must be determined by the end customer/ buyer in its final application.
28401.0-00
Part No.
STEGO, Inc. · 1395 South Marietta Parkway · Building 800 · Marietta, GA 30067 · Tel: (770) 984-0858 · Fax: (770) 984-0615
IP66 (EN 60529) / IPX9K (EN 40050-9)
Toll free: 1-888-783-4611 (US & Canada only) · www.stegousa.com
DA 284S Stainless Steel Pressure Compensation Device
Protection type
Pressure differentials in a hermetically sealed enclosure are a result of the heat generated by
electrical and electronic components in the enclosure, as well as the fluctuation of the outside
temperature. In the case of negative pressure or vacuum, for example, dust and humidity can
be absorbed through the door seal and can enter the enclosure.
The DA 284S Stainless Steel Pressure Compensation Device provides a protected enclosure
environment for valuable and crucial components with an IP66 rated degree of protection. A
semipermeable membrane inside the device allows air and humidity to leave the enclosure. In
the opposite direction, it only allows dry air into the enclosure while not allowing humidity and
dust from the outside to enter.
| |
High degree of protection
Semipermeable membrane
Corrosion resistant
Easy to install
Technical Data
Mounting
Depth in enclosure
Material
Sealing
Filter
Air permeability
Operating/storage temperature
Dimensions
Protection type
Installation
A hole with a diameter of 1.6 inches (40+0.5mm) is required for mounting. Make sure that the sealing gasket
is placed on the outer side of the enclosure. For optimal pressure compensation, it is recommended to use two
devices on opposite sides towards the top of the enclosure.
2.28” (58 mm)
1 packing unit
1 piece
thread M40 x 1.5 with nut
approx. 0.35” (9mm)
stainless steel V2A (DIN 1.4404 / AISI 316L)
NBR gasket
semipermeable membrane
1200 liters/hr at a pressure difference of min. 70mbar
-49 to +176°F (-45 to 80°C)
Ø 2.28” x 1.22” (Ø 58 x 31mm)
see below
Weight (approx.)
5.6 oz. (160g)
1.22” (31 mm)
0.79” (20 mm)

Related parts for 01230.9-01