Specifications of MCR-S10-50-UI-DCI-NC

Input Type
0 - 9.5A, 0 - 55A
Output Type
Current Or Voltage
No. Of Output Channels
2
Accuracy
± 0.5%
Supply Voltage Range
20VDC To 30VDC
Approval Bodies
CE, UL Recognised
External Depth
114.5mm
External
RoHS Compliant
External Length / Height
99mm
Rohs Compliant
Yes
MCR-S-…-DCI
Current Transducer up to 55 A,
Programmable and Configurable
INTERFACE
Data Sheet
1
MCR-S-…-DCI current transducers offer users the option
of ordering a preconfigured device, configuring the device
themselves via DIP switches or programming it with
MCR/PI-CONF-WIN configuration software
(Order No. 2814799).
The MCR-S-1-5-UI-DCI module provides not only the
standard 1 A and 5 A input signals, but also the option of
setting current ranges of 0 ... 0.2 A to 0 ... 11 A progressively.
With a measuring range of 0 ... 9.5 A to 0 ... 55 A, the
MCR-S-10-50-UI-DCI is ideal for measuring higher motor
currents.
100241_07_en
FL
Description
Observe the safety instructions on page 10.
Make sure you always use the latest documentation.
It can be downloaded at www.download.phoenixcontact.com.
A conversion table is available on the Internet at
www.download.phoenixcontact.com/general/7000_en_00.pdf.
This data sheet is valid for all products listed on the following page:
IN
I
POWER
Phone: +49 - 52 35 - 30 0 • Fax: +49 - 52 35 - 34 12 00 • www.phoenixcontact.com
U,I
PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany
OUT
www.phoenixcontact.com/salesnetwork
© PHOENIX CONTACT - 06/2006
DC, AC, and distorted currents can be equally well
measured.
In addition to an analog output, these current transducers
also have an optional relay and transistor output, e.g., for
alarm monitoring.
When ordering, the desired configuration to which the
device is to be adapted must be specified (see order key on
page 5 and page 8).
Features
Progressive adjustment of measuring range
True r.m.s. value measurement
3-way electrical isolation according to EN 61010
With optional relay and transistor output
22.5 mm ME housing
1

Related parts for MCR-S10-50-UI-DCI-NC

MCR-S10-50-UI-DCI-NC Summary of contents

Page 1

... A and 5 A input signals, but also the option of setting current ranges of 0 ... 0 ... 11 A progressively. With a measuring range of 0 ... 9 ... 55 A, the MCR-S-10-50-UI-DCI is ideal for measuring higher motor currents. Observe the safety instructions on page 10. Make sure you always use the latest documentation. ...

Page 2

... Adapter cable, 9-pos. D-SUB female connector to 25-pos. D-SUB male connector 100241_07_en Type 1 MCR-S-1-5-UI-DCI MCR-S-1-5-UI-DCI-NC With Relay and Transistor Output 1 MCR-S-1-5-UI-SW-DCI MCR-S-1-5-UI-SW-DCI-NC 1 MCR-S-10-50-UI-DCI MCR-S10-50-UI-DCI-NC With Relay and Transistor Output MCR-S-10-50-UI-SW-DCI MCR-S10-50-UI-SW-DCI-NC Type MCR/PI-CONF-WIN MCR-TTL/RS232-E PSM-KAD 9 SUB 25/BS MCR-S-…-DCI Order No. Pcs./Pck. 2814634 1 ...

Page 3

... Technical Data 3.1 Technical Data for MCR-S-1-5-UI(-SW)-DCI(-NC) (Measuring Range 0 A ... 0 ... 11 A) Measuring Input Input current (AC distorted currents) Operate threshold Frequency range Connection method Overcurrent capacity, continuous Surge strength for 1 s Output Output current/load Output voltage/load Switching Output Relay output Contact material ...

Page 4

... EN 61000-4-2 Criterion B EN 61000-4-3 Criterion A EN 61000-4-4 Criterion B EN 61000-4-5 Criterion B EN 61000-4-6 Criterion 55011 Class A MCR-S-…-DCI MCR-S-1-5-UI-SW-DCI(-NC) Green LED IP20 Any Any 22 114.5 mm Polyamide PA, not reinforced air discharge kV/5 kHz 2 2 kV/42 Ω 1 kV/2 Ω ...

Page 5

... Order Key for the MCR-S-1-5-UI(-SW)-DCI Current Transducer If customer order information is incorrect or unavailable, the standard configuration is delivered (shown as an example in the order key). Order No. Measuring Range Start Value 2814634 / MCR-S-1-5-UI-DCI Measuring Measuring Order No. Range Start Range Final Value Value 2814650 / 0. ...

Page 6

... Technical Data for MCR-S-10-50-UI(-SW)-DCI(-NC) (Measuring Range 0 A ... 9 ... 55 A) Measuring Input Input current (AC distorted currents) Operate threshold Frequency range Connection method Overcurrent capacity, continuous Surge strength for 1 s Output Output current/load Output voltage/load Switching Output Relay output Contact material Maximum switching voltage Continuous current carrying capacity If the specified maximum values are exceeded, the gold coating will be damaged ...

Page 7

... Criterion A: Normal operating behavior within the specified limits 55011 corresponds to CISPR11 5 Class A: Industrial application, without special installation measures. 100241_07_en MCR-S-10-50-UI-DCI(-NC) MCR-S-10-50-UI-SW-DCI(-NC PROCESS CONTROL EQUIPMENT FOR HAZARDOUS LOCATIONS 31ZN LISTED Cl. I, Zn. 2, AEx nC IIC IIC T6 Cl. I Div. 2, Groups and D A) This equipment is suitable for use in Class I, Division 2, Groups and D or non-hazardous locations only ...

Page 8

... Order Key for the MCR-S-10-50-UI(-SW)-DCI Current Transducer If customer order information is incorrect or unavailable, the standard configuration is delivered (shown as an example in the order key). Order No. Measuring Range Start Value 2814647 / MCR-S-10-50-UI-DCI Measuring Measuring Order No. Range Start Range Final Value Value 2814663 / 0 ...

Page 9

... MCR-S-1-5-UI-SW-DCI Figure 1 Structure using the example of the MCR-S-...-UI-SW-DCI(-NC) current transducer with relay and transistor output 1 Metal lock for mounting on the DIN rail 2 Upper part of housing slides open for DIP switch setting 3 Programming interface 4 TIME potentiometer for threshold value suppression time (only for MCR-S-...-UI-SW-DCI(-NC)) 5 Yellow " ...

Page 10

... Method of Operation Connection to the input terminal blocks (MCR-S-1-5-...-DCI) or passing the live conductor through the current transducer (MCR-S-10-50-...-DCI) induces a magnetic flux in the strip-wound core. The magnetic flux density is measured using a Hall sensor and converted proportionally from the input current to a voltage (Hall voltage) ...

Page 11

... Ready for operation Figure 2 Configuration flowchart 100241_07_en 5.5.1 The MCR-S-…-DCI generation offers the advantage of a choice between configuration and programming. MCR/PI-CONF-WIN software can be used to freely program the true r.m.s. value current transducer. Programming is described in the software manual. The user-friendly configuration software runs under all popular Windows operating systems ...

Page 12

... Setting the analog output signal Setting the input measuring range 1 1 Only for MCR-S-...-SW-DCI(-NC) Setting DIP switch 10 to configuration mode (DIP switch 10 to "OFF") switches all potentiometers to "active". DIP 10 Description OFF Configuration via DIP switches Programming via software (DIP switches 1 ...

Page 13

... V ... -5 V OFF OFF ON 5.5.5 The relay and transistor output of the threshold value versions (MCR-S-...-SW-DCI) are set after the input measuring range and the analog output have been adapted. DIP 1 DIP 2 Setting the Switching Threshold +25% The diagrams below (Figure 5 to Figure 8 on page 14) illustrate the four possible switching behavior options for the relay and transistor output ...

Page 14

... Relay N/C contact Figure 6 Threshold value condition t Operating voltage Relay N/O contact t and transistor output t Relay N/C contact t Figure 8 MCR-S-…-DCI ( (0) ( (1) Function diagram: Closed circuit current- controlled when above threshold value (1) t (0) (0) t (1) Function diagram: Closed circuit current- ...

Page 15

... Section "Electrical Connection" on page 10. When the green "POWER" LED is lit, the operating voltage … connected. When using the MCR-S-…-DCI, ensure you use the correct signal input terminal block for your measuring range. Signal Input ...

Page 16

... To prevent switching behavior at the binary output level during a brief overcurrent, a suppression time must be set using the TIME potentiometer. If the increased current is present for longer than the specified suppression time, the preselected switching behavior becomes active. The available setting range seconds. PHOENIX CONTACT MCR-S-…-DCI 16 ...

Page 17

... Software Package (Adapter alternative to setting via DIP switches, the module can be programmed using MCR/PI-CONF-WIN configuration software (Order No. 2814799). Software Features – All configuration parameters can be entered in the computer – The parameters entered in the computer can be saved to the measuring transducer – The parameters available in the module can be exported – ...

Page 18

... Lighting Monitoring MCR current transducers can be used for monitoring lighting. If the strength of the current in a circuit is above or below a specified value after a suppressed switch-on time, there is a fault in the lighting circuit. If the lighting circuit fails, this signal status can be passed on to another control unit and the emergency lighting can be switched on. The same method can also be used with other power loads. © ...

Related keywords