MCR-S10-50-UI-DCI-NC Phoenix Contact, MCR-S10-50-UI-DCI-NC Datasheet - Page 12

no-image

MCR-S10-50-UI-DCI-NC

Manufacturer Part Number
MCR-S10-50-UI-DCI-NC
Description
INTERFACE ANALOG
Manufacturer
Phoenix Contact
Datasheet

Specifications of MCR-S10-50-UI-DCI-NC

Input Type
0 - 9.5A, 0 - 55A
Output Type
Current Or Voltage
No. Of Output Channels
2
Accuracy
± 0.5%
Supply Voltage Range
20VDC To 30VDC
Approval Bodies
CE, UL Recognised
External Depth
114.5mm
External
RoHS Compliant
External Length / Height
99mm
Rohs Compliant
Yes
Figure 4
Setting DIP switch 10 to configuration mode (DIP switch 10
to "OFF") switches all potentiometers to "active".
100241_07_en
1
DIP 10
OFF
DIP
ON
Only for MCR-S-...-SW-DCI(-NC)
10
9
8
7
6
5
4
3
2
1
DIP switches
Description
Configuration via DIP switches/
programming via software
Input current measurement: true r.m.s.
value/arithmetic average value
Operating current/closed circuit current
behavior
Above threshold value/
Below threshold value
Setting the analog output signal
Setting the input measuring range
Description
Configuration via DIP switches
Programming via software (DIP switches 1
to 9 and potentiometer settings not
relevant)
1
1
DIP
10
...
1
5.5.3
(Rough setting via DIP switches)
Use DIP switch 9 to select the measuring process (true
r.m.s. value or arithmetic average value).
True r.m.s. value: The true r.m.s. value of an AC current
corresponds by definition to the steady-state value that
results from the instantaneous values of this current. This
steady-state value generates the same thermal work in an
ohmic resistor as a DC current of identical magnitude. The
term "true r.m.s. value" simply indicates that distorted and
pulsating currents are also measured.
Arithmetic average value:The arithmetic average value is
used to measure DC currents or to filter a DC portion from
a pulsating current. Using the arithmetic average value on
a symmetrical AC current would result in a measured value
with the value "0".
The arithmetic average value can be used to make bipolar
DC currents available as analog standard signals at the
output.
DIP 9
OFF
ON
Configuration of the Input Current Range and
Measuring Process
Description
True r.m.s. value (AC and DC without digit
sign)
Arithmetic average value (DC with digit
sign)