MCR-S10-50-UI-DCI-NC Phoenix Contact, MCR-S10-50-UI-DCI-NC Datasheet - Page 16

no-image

MCR-S10-50-UI-DCI-NC

Manufacturer Part Number
MCR-S10-50-UI-DCI-NC
Description
INTERFACE ANALOG
Manufacturer
Phoenix Contact
Datasheet

Specifications of MCR-S10-50-UI-DCI-NC

Input Type
0 - 9.5A, 0 - 55A
Output Type
Current Or Voltage
No. Of Output Channels
2
Accuracy
± 0.5%
Supply Voltage Range
20VDC To 30VDC
Approval Bodies
CE, UL Recognised
External Depth
114.5mm
External
RoHS Compliant
External Length / Height
99mm
Rohs Compliant
Yes
Adjustment Structure
Figure 12
Example:
The current transducer is to be set to the following values:
Input measuring range:
Output measuring range: 0 mA ... 20 mA I
Constant current for configuration
100241_07_en
I
A
Signal input
= I
After connecting the operating voltage and signal lines,
first adjust the zero point (offset). There should be no
signal at the input (I
The analog output must correspond to a preselected
output signal from the table on page 13. Adjust any
inaccuracies using the ZERO potentiometer.
To adjust the measuring range final value, where
possible a current of the same level as the final value
should be specified. If this is not possible, one of the
following adjustment formulae should be used:
Adjust the calculated output current using the SPAN
potentiometer to I
is used, the same adjustment procedure is necessary.
0
+ (–––
I
ME
I
E
Adjustment structure
x
(I
MA
I
A
E
- I
A
0
))
= 12 mA. When the voltage output
E
= 0).
0 A ... 5 A
MCR-S
U
A
= U
Operating voltage
0
+ (––– x (U
V
U
I
A
I
ME
E
I
I
I
A
A
ME
0
MA
I
E
Signal output
= 5 A
= 0 mA
= 20 mA
= 3 A
MA
- U
0
))
Threshold Value Output
When the yellow "SW" LED lights up (relay and transistor
status display), the N/O contact of the PDT contact is
closed and the N/C contact of the PDT contact is open. The
transistor output switches through.
Specify a current for the module, which corresponds to
the threshold value:
Set the TIME potentiometer to "0 s" and turn the
threshold value potentiometer according to the
following instructions (see Figure 5 to Figure 8 on
page 14):
For Figure 5: Turn the threshold value potentiometer
until the yellow "SW" LED lights up.
For Figure 6: Turn the threshold value potentiometer
until the yellow "SW" LED goes out.
For Figure 7: Turn the threshold value potentiometer
until the yellow "SW" LED goes out.
For Figure 8: Turn the threshold value potentiometer
until the yellow "SW" LED lights up.
To prevent switching behavior at the binary output level
during a brief overcurrent, a suppression time must be
set using the TIME potentiometer. If the increased
current is present for longer than the specified
suppression time, the preselected switching behavior
becomes active. The available setting range is 0 to
20 seconds.
PHOENIX CONTACT
MCR-S-…-DCI
16