PGA-016A Littelfuse Inc, PGA-016A Datasheet - Page 14

no-image

PGA-016A

Manufacturer Part Number
PGA-016A
Description
BULK / WATERTIGHT COVER FOR PGR-6200 / PGR-7200
Manufacturer
Littelfuse Inc
Datasheet

Specifications of PGA-016A

Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
Lead Free Status / RoHS Status
Contains lead / RoHS non-compliant
www.littelfuse.com/series/PGR-4700.html
PGr-4700 SerIeS (rCD300M2)
Sensitive Ground-Fault Relay
See pg. 31-36 for Current Transformer Selection Guide and
Accessory Information.
CONTROL
POWR-GARD
ANALOG %
CURRENT METER
ANALOG
OUTPUT
POWER
+
0-1mA
1
POWR-GARD
SENSITIVE GROUND-FAULT RELAY
PGR-4700 SERIES
9
PGA-0500
(optional)
10
2
11
®
12
4
TEST RESET
GROUND FAULT
13
5
®
14
6
POWR-GARD
GROUND-FAULT
CURRENT
TRANSFORMER
PGC 5000
SERIES
15
7
16
8
®
POWR-GARD
Ground-Fault Protection – Solidly Grounded System (PGr 4000 Family)
12
Description
The PGR-4700 Sensitive Ground-Fault Relay provides
sensitive ground-fault protection without nuisance tripping.
It detects very low-level leakage current on large circuits
to avoid or significantly reduce equipment damage. The
leakages can be identified as they develop and ground faults
can be detected before they become critical.
Applications
Ground-fault relays can be used for the protection of critical
circuits in panel boards and switch boards, OEM power
distribution panels and custom controls. They are typically
used in critical load applications with costly downtime and
hazards, such as high humidity, water, dust, chemicals, and
vibration.
Features/Benefits
Ordering Information
Specifications
IEEE Device Numbers
Input Voltage
Dimensions
Trip level Settings
Trip Time Delay Settings
Contact Operating Mode
Harmonic Filtering
Test Button
reset Button
CT loop Monitoring
relay Contacts
Approvals
Communications
Conformally Coated
Warranty
Mounting
®
PGR-4700-24
PGR-4700-120
PGR-4700-240
Adjustable trip level settings from 10 mA to 3.0 A
Advanced harmonic filtering
Compatible with VFD applications
Adjustable time delay
Metering output with PLC interface for continuous
monitoring of system
CT loop monitoring
Protection Relays, Monitors & Systems
© 2009 Littelfuse
50G, 50N, 51G, 51N
See Ordering Information
H 75 mm (3.0”); W 55 mm (2.2”); D 115 mm (4.5”)
10 mA – 3.0 A
0–1.5 s
Selectable fail-safe or non-fail-safe
(Internal switch)
Standard
Standard
Standard
Standard
2 N.O. and N.C.
UL listed
Analog Output
Optional
5 Year
DIN, Surface
POWR-GARD
24 Vdc Control Power
120 Vac Control Power
240 Vac Control Power
®
Protection Relay Catalog