Troubleshooting
All models other than
Analog I/O Slave
Units
Slave Units to which
Expansion Units can
be mounted
Slave Units with
Operation Time Moni-
tor Function
Slave Units with out-
puts
Slave Units with
inputs
Model
The Maintenance Counter
returned to 0.
Some functions do not change
even after parameters have
been edited or set.
The Maintenance Counter is
not counting even though out-
puts are turned ON.
I/O communications stopped
after mounting or removing an
Expansion Unit and turning ON
the power.
The MS indicator lights red
after mounting or removing an
Expansion Unit online.
The Operation Time Monitor
does not show the expected
values.
The status flag for the Opera-
tion Time Monitor value turns
ON and OFF.
Cannot hold outputs when
communication errors occur.
Cannot clear outputs when
communication errors occur.
There is a delay with the ON
and OFF timing for input val-
ues.
Problem
• The Maintenance Counter will
• The Maintenance Counter will
The functions that have been
changed are enabled only after
the power is cycled.
The I/O power supply is OFF.
The number of I/O points
increase or decrease when
Expansion Units are mounted
or removed. The number of I/O
points may not match the I/O
table registered in the Master
Unit.
Expansion Units cannot be
mounted or removed online.
• If the input filter is set, there is
• The operation time ON or
• The selected operation time
The Operation Time Flag is
refreshed every measurement
cycle, after the operation time
is compared with the monitor
value. The Operation Time
Flag turns ON for one cycle
and turns OFF, if the operation
time drops below the monitor
value at refreshing. There is
another flag that holds the con-
tents of monitor value
exceeded flags.
The Unit is set to clear outputs
for communications errors.
The Unit is set to hold outputs
for communications errors.
An input filter may be set.
return to 0 if the Unit is reset.
always return to 0 when the
setting is switched between
the Total ON Time Monitor
Function and the Contact
Operation Monitor Function.
a delay with the ON or OFF
time.
OFF edge selection may not
be on the intended setting.
combination is not supported.
If the operation time monitor
does not show the expected
values, the settings may be
different from the intended
settings. The accuracy is ±6
ms.
Cause
---
Cycle the power or reset the
CX-Integrator.
Check that the I/O power sup-
ply is turned ON.
Change the Master Unit I/O
table settings.
Turn OFF the power before
mounting or removing Expan-
sion Units.
• Use the Operation Time Mon-
• Check the operation time
---
Change the setting to hold out-
puts for communications
errors.
Change the setting to clear
outputs for communications
errors.
Set the input filter value to 0.
Alternatively, change the input
filter to an appropriate value.
itor function considering the
filter setting or set the filter
constant to 0 ms.
combination set for Slave
Units for which the operation
time edge can be set.
Possible correction
Section 12-2
583