Indicators and Error Processing
9-1
456
MS
NS
MS
NS
MS/NS indicators
MS
NS
NS
MS
MS
NS
MS
NS
Indicators and Error Processing
ON (green)
Flashing (red)
OFF
Flashing (green)
ON (red)
ON (green)
ON (green)
ON (green)
ON (red)
ON (green)
OFF
OFF
Remote I/O communi-
cations or message
communications in
progress
Checking for node
address duplication
Waiting for connection
Watchdog timer error
Switch settings are
incorrect.
Node address duplica-
tion
Details
Remote I/O Commu-
nications or message
communications in
progress
Checking for node
address duplication at
the Master.
Waiting for connec-
tion to be established
with Master.
Watchdog timer error
has occurred in Slave
The DIP switch or
other switch settings
are incorrect.
Slave Unit has been
assigned the same
node address as the
Master Unit.
Remote I/O communications and/or
message communications are being
performed.
(Normal status)
If this indicator status has occurred for
only specific Slaves, check that the
Slave baud rate settings are correct and
then restart them.
Replace the Slave Unit.
Check the switch settings and restart
the Slave Unit.
Reset the Slave Unit so that it has a
unique node address, and then restart
the Slave Unit.
Probable cause and remedy
Section 9-1