NT631C-ST153-EV3 Omron, NT631C-ST153-EV3 Datasheet - Page 77

no-image

NT631C-ST153-EV3

Manufacturer Part Number
NT631C-ST153-EV3
Description
10.48-ColrDisplay,TFT,Ivy,Eng
Manufacturer
Omron
Datasheet

Specifications of NT631C-ST153-EV3

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Connecting to the RS-232C Port at the Host
Connecting to a CS/CJ-
series Serial
Communications Unit
60
RS-232 port
This is used mainly for
connection to the RS-232C
unit.
(This also supports the
CX-Programmer.)
Peripheral port
This is used mainly for
connection to the
Programming Device.
(This also supports the
RS-232C unit connection.)
DM32000
DM32001
DM32002
DM32003
Allocation DM area (words)
Port 1
Connecting to CS-series Serial Communications Board
Serial Communications Board equipped with a RS-232C port for CS-series
CPU Units: CS1W-SCB21(-V1)/41(-V1) (See note.)
Allocation DM Area Settings for CPU Unit
Settings are written from the Programming Device (a Programming Console
or CX-Programmer) directly into the allocation DM area (system setting area)
of the CPU Unit. After the settings are written, they become effective by turn-
ing the power ON, restarting the Unit, restarting the communications port, or
execution of the STUP command.
In the following, the channel numbers of the allocation DM area and the set-
tings are shown.
CS/CJ-series Rack-mounting Unit:
CS1W-SCU21(-V1)
CJ1W-SCU21(-V1)/41(-V1)
Setting the Front-panel Switches
Set the unit number of the Serial Communications Unit by using the rotary
switch located on the front panel. Set each switch with a flat blade screwdriver
so that the values or symbols in the setting value window agree with the fol-
lowing.
DM32010
DM32011
DM32012
DM32013
Note Cannot be used with the CS1D-CPU65H/67H.
Port 2
0000
8000
0000
0007
0000
SYSMAC CS1G
CPU42
PROGRAMMABLE CONTROLLER
PERIPHERAL
Writing Value
OPEN
RUN
ERR/ALM
INH
PRPHL/COMM
MCPWR
PORT
OPEN
BUSY
DIP switches (inside the battery storage)
• Set SW4 to ON (establishing communications in
• Set SW5 to OFF (establishing communications
Host link mode, 2 stop bits, even parity, data
length 7 bits
Communications speed 9600 bps.
Communications speed 19200 bps.
Transmit delay time 0 ms.
No CTS control Unit No.0 for host link
accordance with PC Setup) when connecting the
NT631/NT631C to a peripheral port.
in accordance with PC Setup) when connecting
the NT631/NT631C to a peripheral port.
Settings
Section 4-1