SDV-DM6 AC100/110 Omron, SDV-DM6 AC100/110 Datasheet - Page 112

no-image

SDV-DM6 AC100/110

Manufacturer Part Number
SDV-DM6 AC100/110
Description
Sensor Hardware & Accessories VOLTAGE SENSOR
Manufacturer
Omron
Datasheets

Specifications of SDV-DM6 AC100/110

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Specifications
Note: These figures are percentages of the maximum scale.
110
Item
Allowable input
voltage range
Rated control power
supply voltage
Allowable control
power supply voltage
Ground fault section
Operating time
Power consumption
Reset method
Control
output
Contact capacity
Exterior
Weight
Item
Setting error (See note.) Within 5%
Influence of input
voltage (See note.)
Influence of control
power supply voltage
(See note.)
Influence of temperature
(See note.)
Insulation resistance
Dielectric strength
Lightning impulse
dielectric strength
Vibration (destruction)
Shock (destruction)
Ratings
Characteristics
Ground
fault
section
Undervolt
age
section
DC Fault Detection Relay
voltage
Model
Rated
input
Model
85% to 110% of the rated voltage
24 VDC, 110 VDC
(specific types for each voltage)
85% to 110% of the rated voltage
Operation resistance: 1 to 10 k
(continuously variable)
Reset resistance: 115% max. of the
operating value
1 s max. (for a sudden ground fault with
resistance dropping from infinity to 0
5 W max.
Self-resetting
SPDT
---
200 VAC, 2 A (cos = 0.4)
30 VDC, 2 A (L/R = 7 ms)
Munsell 5Y 7/1
Approx. 330 g
Within 5% (at voltages between 80%
and 120% of the rated voltage)
Within 2% (at voltages between 85%
and 110% of the rated voltage)
Within 5% (at temperatures between
10 M
electric circuits and outer casing)
2,000 VAC, 50/60 Hz for 1 min
(between electric circuits and outer
casing)
1.2/50 s, 4,500 V between electric
circuits and outer casing
16.7 Hz, 1.0-mm double amplitude in 3
directions for 10 min each
294 m/s
10 to 60 C)
24 VDC
min. at 500 VDC (between
2
SDG-A
SDG-A
SDG
110 VDC
)