SDV-DM6 AC100/110 Omron, SDV-DM6 AC100/110 Datasheet - Page 58

no-image

SDV-DM6 AC100/110

Manufacturer Part Number
SDV-DM6 AC100/110
Description
Sensor Hardware & Accessories VOLTAGE SENSOR
Manufacturer
Omron
Datasheets

Specifications of SDV-DM6 AC100/110

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
K2CU-P Small-capacity, Plug-in Models
Specifications
Note: The logical value is an operating value within a range of 0.85 to 1.1 with a voltage fluctuation of 85% to 110%, based on the value at the
56
100/
200 VAC
110/
220 VAC
Control supply voltage
Rated frequency
Carry current
Operating voltage range
Voltage fluctuation compensation
range
Operating current
Releasing current
Operate time
Gate input voltage range (for models
with gate input terminals)
Control output
Power consumption
Setting accuracy
Repeat accuracy
Influence of temperature
Influence of voltage
Influence of frequency
Insulation resistance
Dielectric strength
Overcurrent
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Weight
Ratings
Characteristics
control supply voltage measured as 1.
Control supply voltage
With voltage fluctuation com-
pensation
Without voltage fluctuation
compensation
With voltage fluctuation com-
pensation
Without voltage fluctuation
compensation
Heater Element Burnout Detector
Item
100, 110, 200, 220 VAC
50/60 Hz
1.25 times as large as each model’s maximum op-
erating current
85% to 110% of control supply voltage
85% to 110% of control supply voltage
4 to 10 A, 8 to 20 A, 16 to 40 A, 32 to 80 A (contin-
uously variable)
105% max. of operating current
0.5 s max. (when current changes from 150% to 0%)
5 to 30 VDC
2 A at 220 VAC, SPDT (cos = 0.4)
Input: 0.5 VA max.
Power supply: 5 VA max.
Models without voltage fluctuation compensation:
Models with voltage fluctuation compensation:
10 M
2,000 VAC, 50/60 Hz for 1 min between electric circuits and mounting panel
20 times of max. set value of operating current for 2 s
Destruction: 16.7 Hz, 1-mm double amplitude for 10 min each in X, Y, and Z directions
Destruction: 98 m/s
Operating: –10 C to 55 C (with no icing)
Operating: 45% to 85%
K2CU-F: approx. 390 g; K2CU-P: approx. 300 g
7% max.
3% max.
10% max. (at 20 C 30 C)
is 85% to 110% of the control supply voltage
supply voltage. (see note)
3% max. (at 5% of rated frequency)
3% max. of the value measured at the control supply voltage, on condition that the voltage fluctuation
5% max. of the logical value, on condition that the voltage fluctuation is 85% to 110% of the control
K2CU-P0.5A-A
---
K2CU-P0.5A-B
---
min. (at 500 VDC) between electric circuits and mounting panel
0.25 to 0.5 A
K2CU
2
(approx. 10G)
K2CU-F
K2CU-P1A-A
K2CU-P1-A
K2CU-P1A-B
K2CU-P1-B
0.5 to 1 A
Operating current
100/200, 110/220 VAC
2.5 A for K2CU-P0.5A-A/-B;
5 A
85% to 110% of control supply voltage (applicable
only on models with voltage fluctuation compensa-
tion)
0.25 to 0.5 A, 0.5 to 1 A, 1 to 2 A, 2 to 4 A (contin-
uously variable)
110% max. of operating current
---
Input: 1 VA max.
Power supply: 4 VA max.
K2CU-P2A-A
K2CU-P2-A
K2CU-P2A-B
K2CU-P2-B
1 to 2 A
K2CU-P
K2CU-P4A-A
K2CU-P4-A
K2CU-P4A-B
K2CU-P4-B
2 to 4 A

Related parts for SDV-DM6 AC100/110