The K2CM Motor Protective Relay offers very stable characteristics.
To maintain these characteristics for a long time, the following
inspections are recommended.
Daily Inspection
The purpose of daily inspection is to discover causes of failure
before using the Motor Protective Relay. This inspection depends
somewhat on the perception of the operator as it includes visual
checking, etc.
Periodic Inspection
This inspection is performed by turning OFF the power at regular
intervals to check the aging caused by long-time operation. It is rec-
ommended that periodic inspection is performed once a year.
Motor Protective Relay
External Rectifier
Check for adhesion of dust and foreign objects, damage to wirings by
burning, and loosening of mounting screws.
Cat. No. N121-E1-01
Connections
Motor Protective Relay Adhesion of foreign objects and dust to the
External rectifier
Construction
Operating characteristics
Insulation resistance
Operation check with test
button
Maintenance and Inspection
Classification
Classification
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Loosening, damage, and dust collection at
screw terminals, damage to wiring insulation
sheaths, excessive force applied on wirings,
adhesion of foreign objects to terminal
screws
operation panel, shift of set value, indication
status of operation indicators and trip indica-
tor, presence/absence of front cover, loos-
ening of screws combining rectifier and
control circuits, deformation of case, abnor-
mal temperature on housing surface
Loosing of terminals, unusual odor, discolor-
ation of surface
Adhesion of dust and foreign objects to
terminals, cracks in insulators around
terminal block, burn damage to wirings,
damage to setting knobs, selector
switches, test button, and reset button,
damage to insulators of solderless ter-
minals, rust and discoloration of screw
terminals
Refer to Testing Method.
Between terminals and mounting panel
Checking of operating time, operation
indicators, and trip indicator