Troubleshooting Problems in Modules
9-2-13 Environmental Conditions Check
9-3
Coordinator Module Errors
256
The Power Supply Unit’s POWER indicator is not lit.
The RDY indicators on the Modules do not go ON.
The Coordinator Module’s RUN indicator does not go
ON.
The Power Supply Unit’s RUN output* does not turn
ON.
The Coordinator Module’s RUN indicator is lit.
(*CJ1W-PA205R Power Supply Unit only)
Motion Control Module does not operate or does not
operate properly.
A particular I/O point does not operate.
Error occurs in 8-point or 16-point units.
A particular I/O point stays ON.
None of a particular Module’s I/O points will go ON.
Troubleshooting Problems in Modules
Error condition
Note
Prevent exposure to corrosive gases, flammable gases, dust, dirt, salts, metal
dust, direct sunlight, water, oils, and chemicals.
Environmental Conditions Check
humidity between 10%
temperature below
temperature above
Is atmosphere
Is noise being
Is the ambient
Is the ambient
Is the ambient
acceptable?
controlled?
and 90%?
55 °C?
0 °C?
End
Yes
Yes
Yes
Yes
Yes
PCB short-circuited or dam-
aged.
The power supply line is faulty
An error in program is causing a
fatal error
Internal circuitry of Power Sup-
ply Unit is faulty.
The I/O bus is faulty.
No (See note.)
No
No
No
No
Probable cause
Consider installing in a panel
or improving the installation
location.
Consider using a fan or air
conditioner.
Consider using a heater.
Consider using an air
conditioner.
Install surge suppressor or
other noise-suppressing
equipment at noise sources.
Replace the Power Supply Unit.
Replace the Power Supply Unit.
Correct program
Replace the Power Supply Unit.
Replace the Motion Control
Module.
Remedy
Section 9-3