PowerFlex 40P Technical Data
Power Terminal Block
Terminal Block Specifications
➊ Maximum/minimum sizes that the terminal block will accept - these are not recommendations.
Name
Power Terminal Block
Terminal ➋
R/L1, S/L2
R/L1, S/L2, T/L3
U/T1
V/T2
W/T3
P2, P1
DC+, DC–
BR+, BR–
Important: Terminal screws may become loose during shipment. Ensure that all terminal screws are tightened to the recommended
torque before applying power to the drive.
Single-phase operation requires a 65% derate of drive rated current.
Description
1-Phase Input
3-Phase Input
To Motor U/T1
To Motor V/T2
To Motor W/T3
DC Bus Inductor Connection (C Frame drives only.)
The C Frame drive is shipped with a jumper between Terminals P2 and P1.
Remove this jumper only when a DC Bus Inductor will be connected. Drive
will not power up without a jumper or inductor connected.
DC Bus Connection (Frame C Drives)
Dynamic Brake Resistor Connection
Safety Ground - PE
Frame
B
C
=
Description
All power terminals
All power terminals
Wire Size Range ➊
Maximum
5.3 mm
8.4 mm
Switch any two motor leads to
change forward direction.
2
2
(10 AWG)
(8 AWG)
Minimum
1.3 mm
1.3 mm
2
2
(16 AWG)
(16 AWG)
R/L1
R/L1
S/L2
S/L2
DC- DC+
C Frame
B Frame
DC- DC+
T/L3
T/L3
U/T1
U/T1
BR+ BR-
BR+ BR-
Recommended Torque
1.7-2.2 N-m (16-19 lb.-in.)
2.9-3.7 N-m (26-33 lb.-in.)
V/T2
V/T2
W/T3
W/T3 P2
P1
19