68081 Tyco Electronics, 68081 Datasheet - Page 2

no-image

68081

Manufacturer Part Number
68081
Description
PNEU HEAD COPALUM 8-1/0AWG
Manufacturer
Tyco Electronics
Datasheet

Specifications of 68081

Lead Free Status / RoHS Status
Not applicable / Not applicable
A. Condition 1
See Figure 2, Detail A
Maximum CMA fill for copper conductor should not
exceed 40% of total CMA. For example, six No. 14
solid aluminum 12.14 mm
No. 8 stranded copper 8.10 mm
equals 40,000 Cir Mil. The one No. 8 stranded copper
conductor is approximately 40% of total CMA
20.24 mm
B. Condition 2
See Figure 2, Detail B
A maximum of ten equal size round conductors may
be crimped without removing film insulation.
C. Condition 3
See Figure 2, Detail C
A maximum of six equal size square conductors may
be crimped without removing film insulation.
2
Insulation Piercing COPALUM Terminal and Splice Crimping Heads
NOTE
i
2
A
[40,000] Cir Mil being crimped.
Conductors must always be within CMA limits of
wire barrel.

D
Figure 2
2
[24,000] Cir Mil plus one
B
2
[16,000] Cir Mil

E
C
D. Condition 4
See Figure 2, Detail D
Four identical rectangular conductors, where one
conductor thickness is equal to or greater than 1/4 the
width of one conductor, may be crimped without
removing film insulation.
E. Condition 5
See Figure 2, Detail E
Two identical rectangular conductors, where
thickness of one conductor is equal to or less than 1/4
of the width of one conductor, may be crimped
without removing film insulation.
F. Condition 6
See Figure 2, Detail F
In some instances, it may not be possible to fit a
particular CMA loading into the normally
recommended terminal or splice. In these cases,
where seven or more equal round, or a combination
of solid aluminum and stranded copper conductors
are used, and the total CMA is at least 50% of
maximum CMA of the next larger size terminal or
splice, the larger size may be used. Example: three
No. 14 solid conductors equal about 6.07 mm
[12,000] Cir Mils. This falls within the CMA range of a
12–10 terminal or splice accepting a maximum CMA
of 6.63 mm
not be possible to insert all three conductors into the
recommended terminal or splice. It is possible to
insert all three conductors into a No. 8 size terminal or
splice accepting a CMA range of 6.63–10.52 mm
[13,100–20,800] circular mils. The 6.07 mm
circular mils amounts to 59% loading of the maximum
CMA for No. 8 size terminal or splices. Therefore, No.
8 size terminals or splices may be used.
G. Condition 7
When using a variety of solid conductor sizes, none of
the conductors should vary more than one (1) wire
gage. (Ideally not more than 1/2 wire gage.)
2.4. Wire Preparation
NOTE
1. Select the proper terminal or splice wire size
and crimping head combination for the wire size
being used. See Figure 3.
2. Determine correct terminal or splice wire loading
by referring to Paragraph 2.3, and CMA range
listed in Figure 3.
3. Strip stranded copper wire to dimension
indicated in Figure 3.
i
2
[13,100] circular mils. However, it may
Do not use stranded aluminum wire.
2
408-2433
[12,000]
2
2
A