C200H-OA223 Omron, C200H-OA223 Datasheet - Page 79

no-image

C200H-OA223

Manufacturer Part Number
C200H-OA223
Description
8PT TRIAC
Manufacturer
Omron
Datasheet

Specifications of C200H-OA223

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
The following series of figures and tables provides a complete set of specifications for each Unit of the C200H.
Note that I/O Units may take on one of three different shapes. Thus I/O Units are sometimes referred to as A-shape
I/O Units, B-shape, or E-shape I/O Units. Refer to the figures at the end of the I/O Unit specifications for the exact
dimensions of these three shapes of I/O Unit.
General Specifications
Supply Voltage
Operating Voltage Range
Power Consumption
Surge Current
Output Capacity
Fuse
24 VDC Output
Dielectric Strength
Noise Immunity
Vibration
Shock
Ambient Temperature
Humidity
Atmosphere
Grounding
Degree of Protection
Weight
!
Caution
Item
When conducting an insulation resistance or dielectric strength test, disconnect the power supply
terminals from the LG and GR terminals. Do not conduct a dielectric strength test on the C200H-
CPU03-E, PS211, RT002-P, or RT202 Units. The power supply input line and internal circuit of the
24 VDC Power Supply are not isolated from each other. If a dielectric strength test is conducted,
the Power Supply will be damaged.
100 to 120/200 to 240 VAC selectable
50/60 Hz
85 to 132/170 to 264 VAC
120 VA max. per Rack (Backplane)
Approx. 5 times the normal current
CPU Rack: 3 A 5 VDC (1.6 A supplied to I/O Units)
Expansion I/O Unit Rack: 3 A 5 VDC (2.7 A supplied to I/O Units)
2 A 250 V 5.2 dia. x 20 (MF51NR)
0.3 A 24 VDC
2,000 VAC 50/60 Hz for 1 minute between
AC terminals and housing 500 VAC 50/60
Hz for 1 minute between DC terminals and
housing leakage current: 10 mA max.
1,000 Vp-p, pulse width: 100 ns to 1 ms, rise time: 1 ns
Mechanical durability: 10 to 35 Hz, 1 mm double amplitude (24.5 m/s
directions, for 2 hours each (When mounted on DIN Rail, 16.7 Hz, 1 mm double
amplitude (4.9 m/s
Malfunction durability: 2 to 55 Hz, 19.6 m/s
each (When mounted on DIN Rail, 2 to 55 Hz, 2.94 m/s
minutes each)
98 m/s
Operating: 0° to 55°C (0° to 45°C for Programming Console) Storage: –20° to 65°C
35 to 85% RH (without condensation)
Must be free of the following:
Less than 100 W
Mounted in a panel
6 kg max.
Corrosive gases
Abrupt temperature changes
Direct sunlight
Dust, salt, or metal filings
Water, oil, or chemicals
C200H-CPU01-E, CPU11-E/PS221
2
in X, Y, and Z directions, 3 times each
Refer to Section 4-4 Special Considerations for C200H-CPU11
+10%
Specifications
Appendix B
2
/
) in X, Y, and Z directions, for 1 hour each)
–20%
2
, in X, Y, and Z directions, for 20 minutes
24 VDC
20.4 to 26.4 VDC
40 W max. per Rack (Backplane)
2 A 125 V 5.2 dia. x 20 (MF51NR)
None
See Caution .
2
, in X, Y, and Z directions, for 20
C200H-CPU03/PS211
2
) in X, Y, and Z
65

Related parts for C200H-OA223