C200H-OA223 Omron, C200H-OA223 Datasheet - Page 93

no-image

C200H-OA223

Manufacturer Part Number
C200H-OA223
Description
8PT TRIAC
Manufacturer
Omron
Datasheet

Specifications of C200H-OA223

Lead Free Status / Rohs Status
Lead free / RoHS Compliant
Specifications
Triac Output Unit C200H-OA122-E
Circuit Configuration
Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used as work
Terminal Connections
bits.
Internal
circuit
Fuse: 5 A 125 V (5.2-dia.x20) GGS (Nagasawa)
Output indicator
Max. Switching Capacity
Max. Inrush Current
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Fuse Rating
Power for External Supply
Weight
Dimensions
120 VAC max.
(1.2 A max. 4 A/Unit)
F indicator
Fuse blowout
detection circuit
1.2 A 120 VAC, 50/60 Hz (4 A/Unit)
15 A (pulse width: 100 ms)
30 A (pulse width: 10 ms)
100 mA 10 VAC/50 mA 24 VAC/10 mA 100 VAC
min.
1.5 mA (120 VAC) max.
1.5 VAC max. (50 to 1,200 mA)/ 5 VAC max. (10 to
50 mA)
1 ms max.
1/2 of load frequency+1 ms or less.
1 (8 points/common)
180 mA 5 VDC max.
5 A 125 V (5.2-dia.x20)
N/A
300 g max.
E-shape
L
L
L
L
L
L
L
L
COM
NC
Fuse
0
1
2
3
4
5
6
7
A0
A1
A2
A3
A4
A5
A6
A7
A8
A9
COM
OUT
OUT
120 VAC max.
L
L
Appendix B
79